[1] System configuration
1. Table of compatible indoor units
The table below summarizes the types of indoor units that are compatible with different types of outdoor units.
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
Outdoor
units
Composing units Maximum total capacity
of connectable indoor
units
Maximum number
of connectable in-
door units
Types of connectable in-
door units
72 - - 36 - 108 18 P06 - P96 models
R410A series indoor units
96 - - 48 - 144 24
120 - - 60 - 180 30
144 72 72 72 - 216 36
168 96 72 84 - 252 42
192 96 96 96 - 288 48
216 120 96 108 - 324 50
240 120 120 120 - 360 50