Mitsubishi Electronics PCH30GK Air Conditioner User Manual


 
OC277-67
OPTIONAL PARTS
14
1-2 Feature of program timer
(1) Daily timer function
Daily timer can be set in 30 minutes units for up to 24 hours.
Each unit can be set for unit ON, unit OFF, or setback operation.
(2) Setback operation (PAC-SC32PTA)
Set back operation is useful for reducing running costs
e.g. At a hotel with a 24-hour system
8:00~23:00 Cooling operation with set temperature at 79°F
23:00~8:00 Setback operation with 4 degrees of setback
As shown in the chart on the right, the set temperature rises 4 degrees
automatically during the setback operation. When the setback operation
ends, normal operation will begin.
(3) Weekly timer function
Daily timer function can apply to each day of the week.
1. TIMER
When using a program timer, a program timer adapter (PAC-825AD) is also needed.
(PAC-825AD is included with PAC-SC32PTA.)
1-1 Program timer specifications
83˚F
79
˚F
8:00
Normal
operation
23:00
Setback
operation
8:00
Normal
operation
Part No. PAC-SC32PTA (with set back function)
Model Name Program timer
Parts name Program timer
Parts No. PAC-SC32PTA
Exterior dimensions (inch) 5-4/32x4-23/32x23/32 (130x120x18mm)
Installation Wall mount
Type of clock Quartz
Clock accuracy ±50 second / month at 77°F
Display-Time
-Week
-Timer setting unit
Liquid crystal display
Liquid crystal display
Liquid crystal display
Program cycle 24 hours
Timer setting unit 30 minutes
No. of set points 48 / day
Power rating 5V DC ±5% (Supplied by Remote Controller)
SET/MONITOR
SET
SMTWTFS
MONITOR
PROGRAM TIMER
PAC-SC32PTA
TODAY
ON
WEEKLY
SETTING
OFF
ON
SET BACK
OFF
CLOCK DAILY TIMER
SET BACK
SET BACK
DAILY
SETTING
12 15 18 21 24
0361215
FILTER
CHECK MODE
TEST RUN
Use 5-wire cable
2-wire cable
Connect to CN1 Connect to CN1
4
Connect to indoor unit
1-3 How to connect program timer
(1) Install the program timer next to the remote controller the same way as the remote controller is installed.
(2) Connect the program timer and the remote controller with a 5-wire cable as shown in the figure below
NOTE:While the program timer is connected to the remote controller, the
24hour ON/OFF timer on the remote controller will not operate.
OC277--3.qxp 1.12.14 1:46 PM Page 67