OC277-32
<DRY operation time chart>
Minimum 3 minutes w1
ON
Thermostat
Indoor fan
Auto vane
Booster heater
Compressor
ON
DRY MODE
DRY MODE
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
Operation starts by
POWER button
ON.
Operation stops by
POWER button
OFF.
Room temperature
becomes equal to
set temperature.
Room temperature
rises above set
temperature.
w1 Even if the room temperature rises above the set temperature during this period, the compressor will not start until this period has ended.
2-2 DRY operation
(1) Compressor control
1 3-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2 The compressor runs when room temperature is higher than set temperature.
The compressor stops when room temperature is equal to or lower than the set temperature.
The compressor maintains the previous state when the room temperature minus the set temperature is 0°F or more, or
lower than 2°F.
3 The compressor stops in check mode or during protective functions.
<How to operate>
1 Press POWER ON/OFF button.
2 Press the MODE button to display “DRY”
3 Press the SET TEMP. button to set the desired temperature.
NOTE: The set temperature changes 2°F when the SET TEMP.
button is pressed one time.
Dry 65 to 87°F