Mitsubishi Electronics PAC-YG31CDA Air Conditioner User Manual


 
The initial value of the property of each object is shown.
Object Object Type
Instance
Number
Present Value Note
On/Off (setup)
BO
xxxx01
OFF (0)
On/Off (state)
BI
xxxx02
OFF (0)
Alarm Signal
BI
xxxx03
Normal (0)
Error Code
MI
xxxx04
Normal (1)
Operation Mode (setup)
MO
xxxx05
Fan (3)
Operation Mode (state)
MI
xxxx06
Fan (3)
Fan Speed (setup)
MO
xxxx07
Low (1)
Fan Speed (state)
MI
xxxx08
Low (1)
Room Temp.
AI
xxxx09
69°F (21)
Set Temp.
AV
xxxx10
69°F (21)
Filter Signal
BI
xxxx11
Off (0)
Filter Signal Reset
BV
xxxx12
Reset (0)
Prohibition of local operation
(On/Off)
BV
xxxx13
Permit (0)
Prohibition of local operation
(Mode)
BV
xxxx14
Permit (0)
Prohibition of local operation
(Filter Reset)
BV
xxxx15
Permit (0)
Prohibition of local operation
(Set Temp)
BV
xxxx16
Permit (0)
Communication State
BI
xxxx20
Normal (0)
System Forced Off
BV
xx9921
Release (0)
Air Direction (setup)
MO
xxxx22
Horizontal (1)
Air Direction (state)
MI
xxxx23
Horizontal (1)
Notification Class
Notification Class
000003
-
Device
Device
000003 -
A
pp
endix 2: Initial Value