8.9 System Setup
The extended function of a system is set up.
Parameter Contents Value
Unit Of temperature It is on BACnet communication and is the
temperature unit to be used.
Initial setting: degrees-Fahrenheit (°F)
Select item: degrees-Fahrenheit (°F) /
degrees-Celsius (°C)
Use Drive Mode Type Dry It checks, when using operation mode type “Dry”
Initial setting: Not used the Dry mode
Check Off: Not used the Dry mode.
Check ON: Used the Dry mode
Use Speed Type
Mid2/Mid1
It checks, when using air speed type “Mid2” and
“Mid1”.
Initial setting: Not used Mid2/Mid1
Check Off: Not used Mid2/Mid1
Low < High
Check ON: Used Mid2/Mid2
Low < Mid2 < Mid1 < High
G-50 Time
Synchronization
If BACnet IF receives the TimeSynchronization
message from BMS when it is checked, the date
and time will be transmitted to G-50A.
When it check, set the date and time to G-50A,
When using this function, be sure to set the
“Time Server IP Address”.
Initial setting: Not set the data to G-50A
Check Off: Not set to G-50A
Check On: Set to G-50A
[Automatically] Reboot *1 It checks, when using the automatically reboot.
When automatic reboot was set to On, it
reboots automatically at the day of the
week and time, which are the set-up cycle
and were set up.
Initial setting: Not auto reboot
(Recommendation)
Check Off: Not auto reboot
Check On: Automatically reboot
Parameter range
[Week] 0 to 99 weeks
[Day of Week] SUN, MON, ... , SAT
[Time] Time (00 to 23) Minute (00 to 59)
*1 When automatic reboot is set up, please set up the automatic login of Windows XP, and automatic starting of BACnet.
When a BACnet IF is started automatically, set the program into the start menu.
Note:
・ “G-50 Time set” is not performed when using “Energy monitoring function (Activate)” or “Summer Time Set-
up (Activate) “ by Integrated centralized control software TG-2000A.
・ When Windows XP OS is used continuously without restarting, system errors may accumulate. Thus it is
necessary to restart both BACnet IF and the OS.
・ The automatic restart function serves to insure that the system restart is done on a regular basis. If there is
an error during the automatic restart, the system must be restarted manually. Since there is a possibility of
the error not being detected, it is recommended to periodically restart the system manually.
・ When automatic reboot is set to [ON], Windows reboots automatically with the set-up cycle.
・ During starting of BACnet IF, abnormalities may be detected by BAS. Therefore, please carry out after
contacting an administrator, in case it works.