8.9 System Setup
The extended function of a system is set up.
Parameter Contents Value
Unit Of temperature It is on BACnet communication and is the
temperature unit to be used.
Initial setting: degrees-Fahrenheit (°F)
Select item: degrees-Fahrenheit (°F) /
degrees-Celsius (°C)
Use Drive Mode Type Dry It checks, when using operation mode type “Dry”
Initial setting: Not used the Dry mode
Check Off: Not used the Dry mode.
Check ON: Used the Dry mode
Use Speed Type
Mid2/Mid1
It checks, when using air speed type “Mid2” and
“Mid1”.
Initial setting: Not used Mid2/Mid1
Check Off: Not used Mid2/Mid1
Low < High
Check ON: Used Mid2/Mid2
Low < Mid2 < Mid1 < High
G-50 Time
Synchronization
If BACnet IF receives the TimeSynchronization
message from BMS when it is checked, the date
and time will be transmitted to G-50A.
When it check, set the date and time to G-50A,
When using this function, be sure to set the
“Time Server IP Address”.
Initial setting: Not set the data to G-50A
Check Off: Not set to G-50A
Check On: Set to G-50A
[Automatically] Reboot *1 It checks, when using the automatically reboot.
When automatic reboot was set to On, it
reboots automatically at the day of the
week and time, which are the set-up cycle
and were set up.
Initial setting: Not auto reboot
(Recommendation)
Check Off: Not auto reboot
Check On: Automatically reboot
Parameter range
[Week] 0 to 99 weeks
[Day of Week] SUN, MON, ... , SAT
[Time] Time (00 to 23) Minute (00 to 59)
*1 When automatic reboot is set up, please set up the automatic login of Windows XP, and automatic starting of BACnet.
When a BACnet IF is started automatically, set the program into the start menu.
Note:
“G-50 Time set” is not performed when using “Energy monitoring function (Activate)” or “Summer Time Set-
up (Activate) “ by Integrated centralized control software TG-2000A.
When Windows XP OS is used continuously without restarting, system errors may accumulate. Thus it is
necessary to restart both BACnet IF and the OS.
The automatic restart function serves to insure that the system restart is done on a regular basis. If there is
an error during the automatic restart, the system must be restarted manually. Since there is a possibility of
the error not being detected, it is recommended to periodically restart the system manually.
When automatic reboot is set to [ON], Windows reboots automatically with the set-up cycle.
During starting of BACnet IF, abnormalities may be detected by BAS. Therefore, please carry out after
contacting an administrator, in case it works.
32