882108-YIM-B-1012
Johnson Controls Unitary Products 39
575-3-60
E4 40 1 40 4 9.0 78 14 4 2.2
10 11
7.5 9 73 80
10 11 75 80
15 17 83 90
15 17
7.5 9 81 90
10 11 83 90
15 17 89 100
20 22
7.5 9 87 100
10 11 89 100
15 17 95 110
25 27
7.5 9 93 110
10 11 95 110
15 17 101 110
E8 80 2 80 4 9.0 78 14 4 2.2
10 11
7.5 9 103 110
10 11 105 110
15 17 113 125
15 17
7.5 9 111 125
10 11 113 125
15 17 119 125
20 22
7.5 9 117 125
10 11 119 125
15 17 125 125
25 27
7.5 9 123 150
10 11 125 150
15 17 131 150
E1 108 3 108 4 9.0 78 14 4 2.2
10 11
7.5 9 131 150
10 11 133 150
15 17 141 150
15 17
7.5 9 139 150
10 11 141 150
15 17 147 150
20 22
7.5 9 145 150
10 11 147 150
15 17 153 175
25 27 7.5 9 151 175
1.
Minimum Circuit Ampacity.
2.
Dual Element, Time Delay Type.
3.
HACR type per NEC.
TABLE 27: ELECTRICAL DATA 30 TON W/ELECTRIC HEAT AND POWER EXHAUST R-410A (CONTINUED)
Voltage
Electric Heat Option
Compressors
(each)
OD Fan Motors
(each)
Supply Blower
Motor
Pwr Exh Motor
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
Model KW Stages Amps Qty RLA LRA MCC Qty FLA HP FLA HP FLA