TABLE 16: REFRIGERANT FACTORY CHARGE R-410A
UNIT (TONS) MODEL
CHARGE
SYSTEM #1 SYSTEM #2 SYSTEM #3 SYSTEM #4
25 wo/HGBP 13lb 8oz 12lb 8oz 12lb 8oz 12lb 8oz
25 w/HGBP 14lb 12lb 8oz 12lb 8oz 12lb 8oz
30 wo/HGBP 16lb 16lb 8oz 14lb 18lb 4oz
30 w/HGBP 16lb 8oz 17lb 14lb 8oz 18lb 12oz
40 wo/HGBP 17lb 10oz 17lb 10oz 19lb 13oz 19lb 13oz
40 w/HGBP 18lb 2oz 18lb 2oz 20lb 5oz 20lb 5oz
TABLE 17: ELECTRICAL DATA 25 TON BASIC UNIT R-410A
Voltage
Compressors (each) OD Fan Motors
Supply Blower
Motor
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
Qty RLA LRA MCC Qty FLA HP FLA
208-3-60 4 22.4 149 35 4 4.5
7.5 24.2 138 150
10 30.8 146 175
15 46.2 165 200
20 59.4 182 225
230-3-60 4 22.4 149 35 4 4.3
7.5 22 134 150
10 28 142 150
15 42 159 200
20 54 174 225
460-3-60 4 10.6 75 16.5 4 2.15
7.5 11 65 70
10 14 69 80
15 21 77 90
20 27 85 110
575-3-60 4 7.7 54 12 4 1.7
7.5 9 49 50
10 11 51 60
15 17 59 70
20 22 65 80
1.
Minimum Circuit Ampacity.
2.
Dual Element, Time Delay Type.
3.
HACR type per NEC.