Millennium Enterprises Z42 Air Conditioner User Manual


 
882108-YIM-B-1012
Johnson Controls Unitary Products 27
TABLE 18: ELECTRICAL DATA 30 TON BASIC UNIT R-410A
Voltage
Compressors (each) OD Fan Motors
Supply Blower
Motor
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
Qty RLA LRA MCC Qty FLA HP FLA
208-3-60 4 25.0 164 39 4 5.8
10 30.8 162 175
15 46.2 181 225
25 74.8 217 250
20 59.4 197 250
230-3-60 4 25.0 164 39 4 5.8
10 28 158 175
15 42 176 200
25 68 208 250
20 54 191 225
460-3-60 4 12.0 100 19 4 2.9
10 14 77 90
15 21 86 100
20 27 93 110
25 34 102 125
575-3-60 4 9.0 78 14 4 2.2
10 11 59 60
15 17 66 80
20 22 72 90
25 27 79 100
1.
Minimum Circuit Ampacity.
2.
Dual Element, Time Delay Type.
3.
HACR type per NEC.
TABLE 19: ELECTRICAL DATA 40 TON BASIC UNIT R-410A
Voltage
Compressors (each) OD Fan Motors
Supply Blower
Motor
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
Qty RLA LRA MCC Qty FLA HP FLA
208-3-60 4 30.1 255 47 4 5.8
10 30.8 182 200
15 46.2 201 225
20 59.4 218 250
25 74.8 237 300
230-3-60 4 30.1 255 47 4 5.8
10 28 179 200
15 42 196 225
20 54 211 250
25 68 229 250
460-3-60 4 16.7 114 26 4 2.9
10 14 97 110
15 21 105 125
20 27 112 125
25 34 121 150
575-3-60 4 12.2 80 19 4 2.2
10 11 72 80
15 17 79 90
20 22 85 100
25 27 91 110
1.
Minimum Circuit Ampacity.
2.
Dual Element, Time Delay Type.
3.
HACR type per NEC.