TABLE 20: ELECTRICAL DATA 25 TON W/ELECTRIC HEAT R-410A
Voltage
Compressors
(each)
OD Fan
Motors
(each)
Supply Blower
Motor
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
Qty RLA LRA MCC FLA HP FLA Option KW Applied Stages Amps
208-3-60 4 22.4 149 35 4.5
7.5 24.2
E4 40 30 1 83
138 150
10 30.8 146 175
15 46.2 165 200
20 59.4 182 225
7.5 24.2
E8 80 60 2 167
197 225
10 30.8 205 225
15 46.2 225 250
20 59.4 241 300
230-3-60 4 22.4 149 35 4.3
7.5 22
E4 40 36.8 1 92
143 150
10 28 150 150
15 42 168 200
20 54 183 225
7.5 22
E8 80 73.6 2 184
212 250
10 28 220 250
15 42 237 250
20 54 252 300
460-3-60 4 10.6 75 16.5 2.15
7.5 11
E4 40 36.8 1 46
71 80
10 14 75 80
15 21 84 90
20 27 91 110
7.5 11
E8 80 73.6 2 92
106 125
10 14 110 125
15 21 119 125
20 27 126 150
7.5 11
E1 108 99.4 3 125
138 150
10 14 142 175
15 21 151 175
20 27 158 175
575-3-60 4 7.7 54 12 1.7
7.5 9
E4 40 36.8 1 40
62 70
10 11 64 70
15 17 72 80
20 22 78 80
7.5 9
E8 80 73.6 2 80
92 110
10 11 94 110
15 17 102 110
20 22 108 125
7.5 9
E1 108 99.4 3 108
120 150
10 11 122 150
15 17 130 150
20 22 136 150
1.
Minimum Circuit Ampacity.
2.
Dual Element, Time Delay Type.
3.
HACR type per NEC.