13 Troubleshooting
Table 13E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater
Interface
FAULT DESCRIPTION CORRECTIVE ACTION
Temp O/Shoot
(continued)
The temperature rise across the heat
exchanger has exceeded the set
parameters for the water heater.
Verify that the system is full of water and that all air
has been properly purged from the system.
Verify that the water heater is piped properly into the
heating system. Refer to Section 6 - System Piping
for the proper piping methods for the Shield water
heater.
Check for 120 VAC to the water heater pump motor
on a call for heat. If voltage is not present, check the
wiring back to the main control board. Replace the
main control board if necessary.
If 120 VAC is present on a call for heat and the water
heater pump is not operating, replace the pump.
Verify that the water heater pump is set to the proper
speed or that the pump is the proper size.
Reference Section 6 - System Piping for water heater
pump specifications.
Heat exchanger outlet water temperature
has exceeded the maximum outlet water
temperature.
Verify that the system is full of water and that all air
has been properly purged from the system.
Verify that the water heater is piped properly into the
heating system. Refer to Section 6 - System Piping
for the proper piping methods for the Shield water
heater.
Check for 120 VAC to the water heater pump motor
on a call for heat. If voltage is not present, check
wiring back to the main control board. Replace the
main control board if necessary.
If 120 VAC is present on a call for heat and the water
heater pump is not operating, replace the pump.
Replace the main control board.
Parameters
Progr
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
display to reset.)
After downloading parameters from a
laptop, the main control board must be
reset.
Press the ENTER/RESET button on the display
panel.
Blocked Drain
SW
(will retry after 5
minutes. RESET may be
pressed after condition is
corrected.)
The blocked drain switch has detected
excessive condensate build up inside the
unit.
• Check condensate tube from unit to floor drain for
proper installation and obstructions.
Inspect condensate trap for blockage. Clean if
necessary.
Check for loose wiring connection at wire harness
plug.
• Bad blocked drain switch. Replace switch.