Lochinvar SNR200-100 Water Heater User Manual


 
43
10 Start-up
Chlorine concentration less than 200 ppm
1. Do not fill the water heater or operate with water
containing chlorine in excess of 200 ppm.
2. Filling with chlorinated fresh water should be acceptable
since drinking water chlorine levels are much lower.
3. Do not use the water heater to directly heat swimming
pool or spa water.
4. At initial fill and during water heater startup and testing,
check system thoroughly for any leaks. Repair all leaks
before proceeding further.
Check for gas leaks
Before starting the water heater, and
during initial operation, smell near the
floor and around the water heater for gas
odorant or any unusual odor. Remove the
top access panel and smell the interior of
the water heater enclosure. Do not
proceed with startup if there is any
indication of a gas leak. Use an approved
leak detection solution. Repair any leaks at
once.
2" PVC CAP WITH
BLOCKED DRAIN SWITCH
CONDENSATE DRAIN
RETAINING SCREW
CONDENSATE FROM
HEAT EXCHANGER
REMOVABLE CAP
TO CLEAN OUT TRAP
Figure 10-1 Condensate Trap
ƽ WARNING
ƽ WARNING
Propane water heaters only – Your propane
supplier mixes an odorant with the propane
to make its presence detectable. In some
instances, the odorant can fade, and the gas
may no longer have an odor. Before startup
(and periodically thereafter), have the
propane supplier verify the correct odorant
level in the gas.
Inspect/fill condensate system
Inspect/check condensate lines and fittings
1. Inspect the condensate drain line, condensate PVC fittings
and condensate trap.
Fill condensate trap with water
1. Remove the PVC cap retaining screw from the PVC cap
(FIG. 10-1).
2. Remove the 2 inch PVC cap with the switch located at the
top of the trap (FIG. 10-1).
3. Fill with fresh water until the water begins to pour out of
the drain.
4. Replace the cap. Press the cap onto the trap until the cap
makes contact with the drain.
5. Replace the retaining screw.
ƽ WARNING
The condensate trap (FIG. 10-1) must be
filled with water during all times of water
heater operation to avoid flue gas emission
from the condensate drain line. Failure to fill
the trap could result in severe personal injury
or death.
ƽ WARNING
Final checks before starting the water
heater
Read this manual to familiarize yourself with electronic
control module operation. Read pages 45 and 46 for
proper steps to start the water heater.
Verify the water heater and system are full of water and all
system components are correctly set for operation.
Verify the preparation procedures of Section 10, pages 43
and 44 have been completed.
Fill the vent condensate trap with water (removing the
retaining screw in order to remove the 2 inch PVC cap with
the switch located at the top of the trap). Replace the cap.
Press the cap onto the trap until the cap makes contact with
the drain. Replace the retaining screw.
Verify electrical connections are correct and securely
attached.
Inspect vent piping and air piping for signs of deterioration
from corrosion, physical damage or sagging. Verify air
piping and vent piping are intact and correctly installed per
this manual.
Installation & Service Manual
TM
DO NOT adjust or attempt to measure gas
valve outlet pressure. The gas valve is
factory-set for the correct outlet pressure.
This setting is suitable for natural gas and
propane (when configured for LP),
requiring no field adjustment. Attempting
to alter or measure the gas valve outlet
pressure could result in damage to the
valve, causing potential severe personal
injury, death, or substantial property
damage.