Monitoring System
Rack Monitoring System
TECHNICAL D
ESCRIPTION
TECHNICAL DESCRIPTION
2
2.2
Connection options
SENSORS
Temperature (digital)
Humidity (digital)
Combined Humidity and
Temperature sensor (digital)
Vibration
Smoke alram
The RMS has a wide variety of connection options (> 3.3.1):
A Three mains monitoring connections (6-pole plug connector)
B Four digital, potential-free switching outputs (8-pole plug connector)
C
Eight digital, potential-free inputs with 12 V auxiliary voltage (16-pole plug
connector)
D Four digital, potential-free alarm inputs for the connection of differential
signal lines (8-pole plug connector))
E Four modular jacks for temperature or humidity sensor (RJ11)
F Two potential-free UPS switching inputs (4-pole plug connector)
G Ethernet network connection (RJ45 – 10 base T)
H AUX serial interface (SUB-D, 9-pole) to control and monitor external devi-
ces (for example, chipcard reader, UPS, …)
I COM serial interface (SUB-D, 9-pole) as terminal connection
– Temperature range: 0 °C to 60 °C
– Measuring accuracy: ±1 °C
– Recalibration not necessary
– Cable length: 4 m
– Maximum cable length: 20 m
– With mounting hardware
- Humidity range: 10 % to 90 %
relative humidity at 0 °C to 60 °C
– Measuring accuracy: ±3 %
relative humidity
– Recalibration not necessary
– Cable length: 4 m
– Maximum cable length: 20 m
– With mounting hardware
Combination of temperature and
humidity sensor, equipment as
above.
Detects movements and vibrations
of varying intensity.
– Ajustable sensitivity
– Cable length: 4 m
– Maximum cable length: 20m
– With mounting hardware
Optical smoke alarm with German
insurance accreditation (VdS) for
early detection of fires
(producing light smoke).
– Temperature range for
deployment: -20 °C to 75 °C
– Cable length: 4 m
– Maximum cable length: 20 m
– With mounting hardware
RMS
LITE