EXAMPLE CONFIGURATION
EXAMPLE CONFIGURATION
5
43
Monitoring System
Rack Monitoring System
Limited alarm duration for filter 4:
Internal buzzer active for 5
seconds if filter 4 (smoke and
shock sensor) is active
Set input for filter 10 Effect to
“thru” in the Feedback menu..
Specimen output
configuration
Additional fan on DIGITAL OUT 1:
activated if filter 1 trips
(temperature).
Signal horn on DIGITAL OUT 2:
activated if filter 4 (smoke or
shock) or filter 6 (passive infra
red) trip. Second fan on DIGITAL
OUT 3 with hysteresis for tempe-
rature 1: switch on fan if tempe-
rature 1 > 37 °C and do not
switch off until temperature 1 <
25 °C.