LG Electronics LP121CEM-Y8 Air Conditioner User Manual


 
- 25 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
Condensate Disposal Pump Kit
Installation
Part No: AYSB2101
Description
The internal condensate pump serves as a means for
disposing of condensate generated during heat pump
operation by transferring it to the indoor coil. The warm coil
surface and the warm room air help in evaporation of the
condensate while adding humidity to the room.
As with any equipment of this type, the addition of this kit will
decrease the effective heating capacity of the unit. This kit is
not intended for use in seacoast or corrosive environments.
NOTE:
Under extreme high humidity conditions, the internal
condensate pump may not be able to dispose of all the
condensate produced, and condensate would then drip from
the outside of the wall sleeve. If this condensation is
unacceptable, then a drain system (including factory
approved drain kit for the wall sleeve) should be installed.
Receiving
Upon receipt of the product, inspect the shipping carton for
signs of visible damage. Report any damage or shortage to
the carrier and note it on the delivery receipt. Unit must be
stored in its original shipping carton in a dry, secure place
prior to its installation and use.
Installation
The installation and servicing of the equipment referred to in
this booklet should be performed by qualified, experienced
technicians.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects
before servicing. Follow proper lockout/tagout procedures to
ensure the power can not be inadvertently energized. Failure
to disconnect power before servicing could result in death or
serious injury.
Important Note:
The unit OFF switch does not disconnect all electrical power
to this unit.
1. Remove front plastic cover by rotating bottom outward and
then lifting up and out from chassis.
2. Unplug and remove the PTAC chassis from the wallsleeve.
Movethe chassis where the front and back of the chassis
can be easily accessed.
3. Remove the wire junction box cover by removing four
screws and lifting up as shown in figure 31.
4. Remove and set aside the air discharge screen by
unscrewing the 5 screws on the top.
5. Remove the one screws holding the control board cover as
shown figure 32.
Remove the cover by lifting it up so its free from its hinges,
and put aside.
6. Unplug the electric heater connecter located inside the wire
junction box.
Figure 31
Figure 32