Integrated Control Board
G61MP units are equipped with a two−stage integrated
control. This control manages ignition timing and fan off
delays based on selections made using the control DIP
switches and jumpers. The control includes an internal
watchguard feature which automatically resets the ignition
control when it has been locked out. After one hour of con-
tinuous thermostat demand for heat, the watchguard will
break and remake thermostat demand to the furnace and
automatically reset the control to relight the furnace.
DIP Switch Settings −− Figure 53
Switch 1 −− Thermostat Selection −− This unit may be used
with either a single−stage or two−stage thermostat. The
thermostat selection is made using a DIP switch which
must be properly positioned for the particular application.
The DIP switch is factory−positioned for use with a two−
stage thermostat. If a single−stage thermostat is to be used,
the DIP switch must be repositioned.
a − Select OFF" for two−stage heating operation con-
trolled by a two−stage heating thermostat (factory set-
ting);
b − Select ON" for two−stage heating operation con-
trolled by a single−stage heating thermostat. This set-
ting provides a timed delay before second−stage heat
is initiated.
Switch 2 −− Second Stage Delay (Used with Single−
Stage Thermostat Only) −− This switch is used to deter-
mine the second stage on delay when a single−stage ther-
mostat is being used. The switch is factory−set in the OFF
position, which provides a 10−minute delay before second−
stage heat is initiated. If the switch is toggled to the ON
position, it will provide a 15−minute delay before second−
stage heat is initiated. This switch is only activated when
the thermostat selector jumper is positioned for SINGLE−
stage thermostat use.
Switches 3 and 4 −− Heating Blower−Off Delay −− The
heating blower−on delay of 45 seconds is not adjustable.
The heating blower−off delay (time that the blower operates
after the heating demand has been satisfied) can be ad-
justed by moving switches 3 and 4 on the integrated control
board. The unit is shipped from the factory with a heating
blower−off delay of 90 seconds. The heating blower off
delay affects comfort and is adjustable to satisfy individual
applications. Adjust the blower off delay to achieve a sup-
ply air temperature between 90° and 110°F at the exact
moment that the blower is de−energized. Longer off delay
settings provide lower supply air temperatures; shorter set-
tings provide higher supply air temperatures.Table 11 pro-
vides the blower off timings that will result from different
switch settings.
TABLE 11
Heating Blower−Off Delay Switch Settings
Blower Off Delay
(Seconds)
Switch 3 Switch 4
60 Off On
90 Off Off
120 On Off
180 On On
Switch 5 −− Cooling Blower−Off Delay −− The cooling
blower−off delay (time that the blower operates after the
cooling demand has been satisfied) can be adjusted by
moving switch 5 on the integrated control board. The
switch is factory−set in the OFF position, which provides a
cooling blower−off delay of 45 seconds. If the switch is
toggled to the ON position, it will provide a 2−second cool-
ing blower−off delay
On−Board Jumper W951 −− Figure 53
On−board jumper W951, which connects terminals R and O
on the integrated control board, must be cut when the fur-
nace is installed in applications which include a heat pump
unit and a thermostat which features dual fuel use. If the
jumper is left intact, terminal O" will remain energized elim-
inating the HEAT MODE in the heat pump.
On−Board Jumper W915 −− Figure 53
On−board jumper W915, which connects terminals Y1 and
Y2 on the integrated control board, must be cut if two−stage
cooling will be used. If the jumper is not cut the outdoor unit
will operate in first−stage cooling only.
Unit Start−Up
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING
Do not use this furnace if any part has been under-
water. A flood−damaged furnace is extremely dan-
gerous. Attempts to use the furnace can result in
fire or explosion. Immediately call a qualified ser-
vice technician to inspect the furnace and to replace
all gas controls, control system parts, and electrical
parts that have been wet or to replace the furnace,
if deemed necessary.
WARNING
Danger of explosion. Can cause injury
or product or property damage. Should
the gas supply fail to shut off or if
overheating occurs, shut off the gas
valve to the furnace before shutting off
the electrical supply.