Horizontal Venting (Horizontal Termination)
The maximum horizontal run made directly off
the rear of the stove into a standard horizontal
cap (#984 or #985) must be no more than a 9”
section of Simpson Dura-vent (#907B). See Figure
12-1.
The maximum horizontal run made directly off
the rear of the stove into a 14” snorkel cap (#982)
must be no more than a 24” section of Simpson
Dura-vent (#904). See Figure12-3.
The horizontal termination cap must maintain a
3" clearance (80 mm) to any overhead combus-
tible projections 2 1/2" (60 mm) or less. Maintain
12" (300 mm) clearance from projections exceed-
ing 2 1/2". See Figure 13.
Any horizontal run of vent must be level or have a
1/4" (5 mm) rise for every foot (300 mm) of run
toward the termination cap. DO NOT ALLOW THE
VENT TO RUN DOWNWARD, AS THIS CAN CAUSE
HIGH TEMPERATURES AND THE POSSIBILITY OF A
FIRE.
A 1” (26 mm) clearance must be maintained
around all co-axial vent pipe.
For buildings with vinyl siding, a Vinyl Siding
Standoff should be installed between the vent
cap and the exterior wall (Simpson Dura-Vent
#950). The Standoff prevents exposure of the
vinyl siding to excessive heat that can damage
the siding material.
A 10" X 10" (250 mm x 250 mm) square hole is
required to maintain proper vent clearances
through a combustible wall. Simpson Dura-Vent
Wall Thimble #942 installed according to the
manufacturer’s instructions meets clearance
requirements.
DO NOT FILL AIR SPACE WITH ANY TYPE OF
INSULATION.
Do not recess the termination cap into the
exterior wall or siding.
IMPORTANT:
FOLLOW THE INSTALLATION IN-
STRUCTIONS PROVIDED WITH EACH
SIMPSON DURA-VENT COMPONENT.
5 Max.
130 mm
Simpson Dura-Vent
Horizontal Termination
Cap #984 or #985
6 (150 mm) Min. Horizontal
Simpson Dura-Vent #908B
No Draft Restriction Required
OPTION # 2
Figure 12-2. Minimum horizontal run to rear
termination.
10 Max.
250 mm
Simpson Dura-Vent
Horizontal Termination
Cap #984 or #985
9 (230 mm) Max. Horizontal
Simpson Dura-Vent #907B
No Draft Restriction Required
OPTION # 1
Figure 12-1. Maximum horizontal run to rear
termination.
24 (610 mm) Max. Horizontal Run
into 14 Snorkel,
Simpson Dura-Vent #904
Both Draft Restrictors Required
Simpson Dura-Vent
14 Snorkel
Termination #982
OPTION # 3
Figure 12-3. Maximum horizontal run to a snorkel
termination.