Panic Keys
There are three Panic keys (A, B, and C) that, if programmed, can be used to manually initiate
alarms and send a report to the central station by pressing and holding the appropriate key for at
least 2 seconds. Each key can be programmed for 24-hour Silent, 24-hour Audible, Fire, or Personal
Emergency responses. The Panic keys are identified by the system as follows:
Keys Displayed as Zone
[A] (∗/1)
95
[B] (∗/#)
99
[C] (3/#) 96
IMPORTANT: For a Silent panic function (if programmed) to be of
practical value, you must program a report code for the zone and the
system must be connected to a central station.
Various System Trouble Displays
Alpha Display Fixed Disp. Meaning
ALARM CANCELED CA will appear if an exit or interior zone contained a fault during closing at the time
the Exit Delay ended (e.g., exit door left open), but the system was disarmed during
the Entry Delay time. The alarm sounder and keypad sound continuously, but stop
when the system is disarmed. No message will be transmitted to the central station.
EXIT ALARM EA will appear when the Exit Delay ends if an exit or interior zone contained a fault
during closing. The alarm sounder and keypad sound continuously until the system
is disarmed (or timeout occurs). An “Exit Alarm” message is sent to the central
station.
Also results if an alarm from an exit or interior zone occurs within 2 minutes after
the end of an Exit Delay.
CHECK CHECK indicates that a problem exists with the displayed zone(s) and requires attention.
ALARM 1xx 1xx indicates that communication between control and a zone expander or wireless
FAULT 1xx 1xx receiver is interrupted, where “xx” is the device address. Check the wiring and
CHECK 1xx 1xx DIP switch settings on the units.
91 If field *199 is set to “1,” all ECP module problems are displayed as “91.”
If there are wireless sensors in the system, the Check condition may also be caused
by some change in the environment that prevents the receiver from receiving
signals from a particular sensor.
SYSTEM LO BAT BAT with no zone number indicates that the system's main standby battery is weak.
LO BAT BAT with a zone number and a once-per-minute beeping at the keypad indicates that a
low-battery condition exists in the wireless sensor displayed (zone “00” indicates a
wireless keypad). If the battery is not replaced within 30 days, a “CHECK” display
may occur.
NOTE: Some wireless sensors use a non-replaceable long-life battery which requires
replacement of the entire unit at the end of battery life (e.g., 5802, 5802CP).
Busy-Standby dl If this remains displayed for more than 1 minute, the system is disabled.
Modem Comm CC The system is in communication with the central station for change of function or
status verification.
no display no display Power Failure
If there is no keypad display at all and the LEDs are unlit, operating power (AC and
battery) for the system has stopped and the system is inoperative.
If the message “AC LOSS” (Alpha display keypads) or “NO AC” (Fixed-Word display
keypads) is displayed, the keypad is operating on battery power only.
If the battery standby capacity is used up during a prolonged AC power outage, the
control's power will shut down to minimize deep discharge of the battery.
Comm. Failure FC A communication failure has occurred.
Open Circuit OC The keypad is not receiving signals from the control and sees an open circuit.
Long Rng Trbl bF Backup LRR communication failure.
Bell Failure 70 Bell supervision failure.
RCVR Jam 90 RF jam detected.
KEYPAD LOW BAT 00 BAT Wireless keypad low battery
Phone Okay Cd The dialer test has been successful (CID code 601).
Dialer Off dO The dialer is disabled.
Test in Progress dd Walk test mode is active(CID code 607).
Upload Completed dC The upload or download session was completed.
Upload Failed dF The upload or download session failed before completion.
Installation Instructions
6-6