– 7 –
*80 *81 SYSTEM NON-ALARM CODES
Enter 00-09; B-F (11-15).
Default = 00 for all reports
*80 1st Digit *81 2nd Digit
Close
|
|
Open
|
|
Low Battery
|
|
Low Battery Restore
|
|
AC Loss
|
|
AC Restore
|
|
Test
|
|
Power Up
|
|
Cancel
|
|
Program Tamper
|
|
*83 FIRST TEST REPORT TIME | | |
[Day 00; hour 12; min 00] Days 01-07 Hours 00-23 Min 00-
59; 00 in all boxes = instant (Day 01= Monday)
*84 SWINGER SUPPRESSION [03] |
01-15 alarms
Must be "00" (disabled) for UL.
*85 ENABLE DIALER REPORTS FOR PANICS & DURESS
1=enable; [0=disable]
995
996
999
Duress
*87 ENTRY WARNING [1]
1=continuous; 0=3 beeps
*86 4208 MODULE ZONE ASSIGMENT [0]
1 = allows 8 zones on one module (10-17), but prevents any
other polling loop expansion. 0 = all other setups.
*88 BURG. ALARM COMM. DELAY [0]
1=16 seconds; 0=no delay
Must be "0" for UL installations.
*89 RESTORE REPORT TIMING [0]
0=Instant; 1=At bell timeout if zone is restored; 2=when
system is disarmed. Must be "0" for UL installations.
*90 SEC. SUBS. ACCT # | | | |
Enter 00-09; B-F (11-15) [15 15 15 15]
2nd Page Programming Fields (press *94)
1*01 1*09 ASSIGN RESPONSE TYPE FOR ZONES.
Skip these fields. Use #93 Menu Mode, Zone
Programming to program the response types.
MISCELLANEOUS WIRELESS OPTIONS
Fields 1*28 - 1*31 are not applicable for UL installations.
1*28 RF TX LOW BATTERY SOUND [0]
1=immediate; 0=when disarmed
1*29 RF TX LOW BATTERY REPORTING [0]
1=enable; 0=disable
1*30 RF RCVR CHECK-IN INTERVAL [06] |
02-15 times 2 hours; 00 disables supervision
1*31 RF XMITTER CHECK-IN INTERVAL [12] |
02-15 times 2 hours; 00 disables transmitter supervision
1*33 TOUCHTONE W/ROTARY BACKUP [0]
1=enable; 0=disable
1*34 COMM. SPLIT REPORTING [0]
0=no; 1=alarms and alarm restores primary, others secondary;
2=open/close, test secondary, others primary. See
51 for
comments if using with dual reporting.
1*40 1*41 NON-ALARM DIALER CODES
Enter 00-09; B-F (11-15).
Default = 00 for all reports
1*40 1st Digit 1*41 2nd Digit
Armed STAY
|
|
Time/Date Set or Event Log Reset
|
|
1*43 PERM. KEYPAD BACKLIGHT [0]
1=enable; 0=disable When disabled, display lights when any
key is pressed, and turns off after period of keypad inactivity.
1*44 WIRELESS KEYPAD TAMPER [0]
DETECTION
1=enable; 0=disable.
Must be "0" for UL installations.
1*45 EXIT DELAY SOUNDING [0]
1=enable; 0=disable. Produces quick beeping during exit
delay if enabled.
NOTE: See page 32, “SOUND OPTION”, prompt for
disabling the entry/exit beeps on individual keypads.
1*46 AUXILIARY OUTPUT MODE [0]
Enter 0 for ground start output.
Enter 1 for open/close trigger.
Enter 2 for keypad-like sounding.
Enter 3 if AAV module is being used.
NOTE: Only one of the above options may be active within
the system.
1*47 CHIME ON EXTERNAL SIREN [0]
1=enable; 0=disable
1*48 WIRELESS KEYPAD ASSIGNMENT [0]
0=disable; enter partition in which RF keypad used, 1-2.
Must be "0" for UL installations.
1*49 SUPPRESS TX SUPERVISION SOUND [1]
1=disable; 0=enable.
Must be "0" for UL installations.
1*52 SEND CANCEL IF ALARM + OFF [0]
1=no restriction; 0=within bell timeout period only
1*53 DOWNLOAD CALLBACK [0]
1=callback not required; 0=callback required.
1*57 5800 RF BUTTON GLOBAL ARM [0]
1=enable; 0=disable