Honeywell 2-Partitioned Security System Home Security System User Manual


 
5
VISTA-40 Programming Form
Some fields are programmed for each partition (shown as shaded fields). If you are programming a multiple-partition system,
see the Partition-Specific Fields section for programming these fields. Standard default (*97) values are shown in brackets.
*00 INSTALLER CODE | | |
Enter 4 digits, 0-9 [4140]
*02 *05 RESPONSE TYPES FOR ZONES
Skip these fields. Use #93 Menu Mode, Zone
Programming to program the response types.
*09 ENTRY DELAY #1 [02] |
00, 02-15 times 15 seconds
Maximum "03" for UL.
*10 EXIT DELAY #1 [03] |
00, 03-15 times 15 seconds
Maximum "04" for UL installations.
*11 ENTRY DELAY #2 [06] |
00, 02-15 times 15 seconds (must be longer than Entry Delay
#1). Maximum "03" for UL installations.
*12 EXIT DELAY #2 [08] |
00, 03-15 times 15 seconds (must be longer than Exit Delay
#1). Maximum "04" for UL installations.
*13 ALARM SOUNDER DURATION [04] |
01-15 times 2 minutes. Must be minimum 16 minutes for UL
installations.
*14 ZONE 9 RESPONSE TIME [0]
Enter 1 for fast response time 10ms
Enter 0 for normal response time 350ms.
Must be 0 for UL installations.
*15 KEYSWITCH ASSIGNMENT [0]
Enter partition in which keyswitch used,
1-2; 0=disable
*16 CONFIRMATION OF ARMING DING [0]
1=enable; 0=disable.
Must be "1" for UL Installations.
*17 AC LOSS KEYPAD SOUNDING [0]
1=yes; 0=no
*19 RANDOMIZE AC LOSS REPORT [0]
1=10-40 min; 0=normal report (about 2 min. after AC loss).
*20 VIP MODULE PHONE CODE | |
Enter 01 - 09 for the first digit; enter [00], [11]
11 for * or 12 for # for the second digit.
Must be set to "0" for UL installations.
*21 PREVENT FIRE TIMEOUT [0]
1=No timeout; 0=Timeout.
*22 KEYPAD PANIC ENABLES [001]
1=enable; 0=disable 995 996 999
*23 MULTIPLE ALARMS [1]
1=yes; 0=no
*24 IGNORE EXPANSION ZONE TAMPER [0]
1=Ignore; 0=Enable tamper for RF and RPMs.
Must be "0" for UL installations if using these devices.
*25 BURG.TRIGGER FOR RESPONSE TYPE 8 [1]
1=enable; 0=disable
*26 INTELLIGENT TEST REPORTING [0]
1=yes (no report sent if any other report was recently sent);
0=no (send report at programmed interval, field *27)
Must be 0 for UL installations.
*27 TEST REPORT INTERVAL [024] | |
Enter interval in hours, 001-199; 000=no report;
Max. 024 for UL installations.
*28 POWER UP IN PREVIOUS STATE [1]
1=yes; 0=no; "1" for UL installations.
*29 QUICK ARM [1]
1=yes; 0=no
*30 TOUCHTONE OR ROTARY DIAL [0]
1=TouchTone; 0=rotary
*31 PABX ACCESS CODE | | | |
00-09; B-F (11-15)
*32 PRIM. SUBS. ACCT # | | | |
Enter 00-09; B-F (11-15) [15 15 15 15]
*33 PRIMARY PHONE NUMBER
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2 second pause
*34 SECONDARY PHONE NUMBER
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2 second pause
*35 DOWNLOAD PHONE NO.
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2 second pause
*36 DOWNLOAD ID NO.
|
| | | | | | |
Enter 00-09; A-F (10-15) [15 15 15 15 15 15 15 15]
*37 DOWNLOAD COMMAND ENABLES
Dlr Shtdwn
Sys Shtdwn
0
Not Used
Rmt Byp
Rmt Disarm
Rmt Arm
Upld Pgm
Dwnld Pgm
See field 1*53 for Callback disable option; [1=enable];
0=disable. For UL installations, all entries must be "0."
*38 PREVENT ZONE XX BYPASS [00] |
01-64; 00 if all zones can be bypassed