Heat & Glo LifeStyle SUPREME-N-I30AU Electric Heater User Manual


 
Heat & Glo • Supreme-N-I30AU, Supreme-P-I30AU • 2222-900 Rev. P • 6/1220
B. MantelandWallProjections
WARNING! Risk of Fire! Comply with all minimum clear-
ances to combustibles as specied. Framing or nishing
material closer than the minimums listed must be construct-
ed entirely of noncombustible materials (i.e., steel studs,
concrete board, etc).
Clearance to combustible material under the insert is 1/4
in. (6 mm). Clearance from top of replace opening for
combustibles extending 12 in. (305 mm) max. is 12 in
(305 mm)
• Use leveling legs to raise insert minimum 1/4 in. (6 mm)
above combustible material or outer wrap of factory built
rebox.
Combustible facings must not extend behind the insert
surround. For non-combustible material specications
refer to Section 1.E.
Figure5.4MantelClearancesorOtherCombustiblesAbove
Appliances
12 in.
(305 mm)
MIN.
12 in.
(305 mm)
MAX.
NON-COMBUSTIBLE FACING
MINIMUM CLEARANCE
TO COMBUSTIBLE
MANTEL OR
PROJECTION
Figure5.3FireplaceOpening-DeepSurround
C
D
SURROUND
APPLIANCE
1-1/2 in.
(38 mm)
B
D
A
D
APPLIANCESURROUND
SIDE VIEW TOP VIEW
MINIMUMFIREPLACESIZE(1-1/2IN.(38mm)SurroundDepth)
Location
SUPREME-I30AU
Inches Millimeters
A
D
Alternate Unit Width 29-1/16 738
B
D
Alternate Unit Depth 13-7/8 352
C
D
Alternate Unit Height 19-1/16 484
* Note: If exhaust collar on insert and replace damper do not line up, add 4 in. (102 mm) to minimum replace
height for bends in vent pipe.