Heat & Glo LifeStyle BAY-40 Indoor Fireplace User Manual


 
Heat & Glo • Multi-Sided Woodburning Fireplace • 34977 Rev T • 11/07
12
E. Construct the Chase
A chase is a vertical boxlike structure built to enclose the re-
place and/or its vent system. Vertical chimneys that run on
the outside of a building must be installed inside a chase.
Construction of the chase may vary with the type of build-
ing. These instructions are not substitutes for the require-
ments of local building codes. Local building codes MUST
be checked.
Chases should be constructed in the manner of all outside
walls of the home to prevent cold air drafting problems. The
chase should not break the outside building envelope in any
manner. All outer walls need to be insulated.
Building codes require false ceiling and ceiling restops at
each oor of the chase or every 10 ft (3.05 m) of clear space
to control spread of re.
Walls, ceiling, base plate and cantilever oor at the rst level
of the chase should be insulated. See Figure 3.5. Vapor and
air in ltration barriers should be installed in the chase as per
regional codes for the rest of the home. Additionally, Hearth
& Home Technologies recommends that the inside surfac-
es be sheet rocked and taped (or the use of an equivalent
method) for maximum air tightness.
Ceiling
Firestop
Metal Chase Top
Round Termination Cap
False Ceiling
Figure 3.5 Chase Assembly
F. Chimney Requirements
When planning your replace location, the chimney con-
struction and necessary clearances must be considered.
The replace system and chimney components have been
tested to provide exibility in construction. Vertical distances
are measured from the base of the replace as shown in
Figure 5.2.
1
2
Figure 3.6 Chase Constructions
1. Fireplace and chimney enclosed in an exterior chase.
2. Chimney offset through exterior wall and enclosed in
chase.
3. Chase constructed on roof.
Gas line holes and other openings should be caulked with
high temperature caulk or stuffed with unfaced berglass in-
sulation. If the replace is being installed on a cement slab,
we recommend that in cold climates, a sheet of plywood or
other raised platform be placed underneath to prevent con-
ducting cold up into the room.
Three examples of chase applications are shown in Fig-
ure 3.6.
Minimum overall straight height 14 (4.27 m)
Minimum height with offset/return 16.5 ft (5.03 m)
Maximum height 90 ft (27.43 m)
Maximum chimney length between an offset
and return
20 ft (6.1 m)
Maximum distance between chimney
stabilizers
35 ft (10.67 m)
Double offset/return minimum height 20 ft (6.1 m)
Maximum unsupported chimney length
between the offset and return
6 ft (1.83 m)
Maximum unsupported chimney height above
the replace
35 ft (10.67 m)
Maximum unsupported chimney above roof 6 ft (1.83 m)
Note: A maximum of two pairs of offsets and returns may
be used.