Heat & Glo LifeStyle 50 Indoor Fireplace User Manual


 
42
E. Combustible Mantel
See Figure 12.11.
A combustible mantel may be positioned no lower than 22 in. (508 mm) above the top of the replace opening.
A combustible mantel may have a maximum depth of 12 in. (305 mm).
Combustible trim and mantels cannot be placed within 6 in. (152 mm) of the replace opening (top or sides).
Combustible materials projecting more than 1-1/2 in. (38 mm) shall not be placed within 12 in. (305 mm) from the top of
the replace opening.
Combustible trim must not cover the metal surfaces of the replace.
Mantel clearance is in accordance with Section 7-3.3.3 of ANSI/NFPA211.
7 ft (2134 mm)
minimum
floor to ceiling
Combustible Wall
2 x 4 stud header
Standoffs
Measured from top of fireplace opening
12 in./305 mm MAXIMUM
22 in./559 mm MINIMUM
Noncombustible Decorative Facing
Seal joint with
non-combustible sealant
Figure 12.11 Clearances to Mantels or other Combustibles above Fireplace
Heat & Glo • RUTHERFORD-50 • 4059-333 Rev C • 06/08