Heat & Glo LifeStyle 50 Indoor Fireplace User Manual


 
31
1/2 in. air space
established by
spacers
Chase Top
Flashing
1/2 in.
Air Space
(Not furnished by
Dura-Vent) Fabricated
Spaces Locally
1/2
Storm collar must
be installed 1 in.
off chase top
Figure 9.4 Chase Top Construction
B. Install Fireplace & Chimney
Install as per Sections 7 and 8.
C. Install Chase Top Flashing
You MUST use a chase top ashing in a chase installation.
Chase top ashings are available from your Heat & Glo
dealer or may be eld constructed.
1 1/2
Figure 9.5 Chase Top Construction
6 in. Min.
Figure 9.6 Chase Top Construction
D. Install Termination Cap
Install the chimney sections up through the chase enclo-
sure.
Install termination caps following instructions provided
with them.
For chase enclosures, use a chase top ashing. The chase
top ashing allows for a 1 1/2 in. (38 mm) clearance around
the outside of the chimney pipe for ventilation air. Install the
chase top ashing at the top of the chase with a 1/2 in. (13
mm) air clearance off the top of the chase constructions
(Figure 9.4, 9.5). Use spacing clips to ensure the 1/2 in.
(13 mm) air clearance. If the chase top ashing does not
t the dimensions of the chase, a custom ashing can be
eld-fabricated as long as it has the same dimensions as
noted in Figure 10.1. Secure the chase top ashing to the
chase with at least three screws or nails per side. When
installed, the bottom of the termination cap must be at least
6 in. (152 mm) above the chase top ashing (Figure 9.6).
WARNING! Risk of Fire! The minimum overlap of cap
to pipe (as shown in the following illustrations) MUST be
met or chimney may separate from cap. Separation al-
lows sparks, heat and embers to escape.
NOTICE: Paint the termination cap with a rust-resistant
paint to protect against the effects of corrosion on those
parts exposed to the weather.
Heat & Glo • RUTHERFORD-50 • 4059-333 Rev C • 06/08
¨