Heat & Glo LifeStyle 2197-980 Indoor Fireplace User Manual


 
Heat & Glo • SOHO-N-AUB • 2197-980 Rev. F • 5/1228
Top Vent - Vertical Termination
This model is approved to use SLP Series ue pipe com-
ponents. A SLP-TVHW vertical Termination Cap must be
used to terminate ue systems in a vertical position.
Approved ue system components are labeled for identi-
cation. NO OTHER FLUE SYSTEMS OR COMPONENTS
MAY BE USED. Detailed installation instructions are in-
cluded with each ue termination kit and should be used
in conjunction with this manual.
WARNING! Risk of Fire! This gas appliance and ue
assembly must be ued directly to the outside and must
never be attached to a chimney serving a separate solid
fuel burning appliance. Each gas appliance must use a
separate ue system-common ue systems are prohibited.
WARNING! Risk of Fire! DO NOT apply combustible
materials beyond the minimum clearances. Comply with
all minimum clearances to combustibles as specied in
this manual. Overlapping material could ignite and will in-
terfere with proper operation of doors and louvers.
Horizontal sections 3 inches (76.2 mm) from the top of
the pipe.
Horizontal sections 2-1/2 inches (63.5 mm) at wall
shield restops.
Horizontal sections 1 inches (25.4 mm) from sides and
bottom of the pipe.
Vertical sections 1 inches (25.4 mm) on all sides of
pipe.
Failure to keep insulation or other material away from vent
pipe may cause over heating and re.
For alternative installations, other than depicted, contact
your dealer for further information.
MODEL FLUE TERMINATION APPROVALS
SOHO-N-AUB SLP-TVHW
Figure 7.6
V
MAX. RUN
38 FT.
(11.58 m)
Straight Up Vertical Flue System
Figure 7.6 shows straight up vertical ue system approved
for use on this model.
If the replace installation requires a vertical
ue exceeding 14-3/4 ft (4.5 m) above the unit
with no horizontal ue or elbows a vertical ue
restrictor must be installed (see Figure 7.7).
CAP
V
1