Heat Controller HEV/H Heat Pump User Manual


 
28
Installation, Operation & Maintenance HEV/H SERIES Heat Controller, Inc.
Table 6: ECM Blower Performance Data Table
Air ow in CFM with wet coil and clean air lter
Model
Max ESP
(in. wg)
Fan
Motor
(hp)
Range
Cooling Mode Dehumid Mode Heating Mode
Fan Only
Mode
Aux/
Emerg
Mode
Stg 2 Stg 1 Stg 2 Stg 1 Stg 2 Stg 1
024 0.75 1/2
Default 750 575 650 500 750 575 350 750
Maximum 850 650 800 600 850 850 850 850
Minimum 600 450 600 450 600 450 300 650
030 0.5 1/2
Default 950 650 800 575 950 650 450 950
Maximum 1100 750 1000 700 1100 1100 1100 1100
Minimum 750 525 750 525 750 525 375 750
036 0.6 1/2
Default 1125 750 975 650 1125 750 525 1125
Maximum 1250 950 1200 800 1250 1250 1250 1250
Minimum 900 600 900 600 900 600 450 900
042 0.6 3/4
Default 1300 925 1125 825 1300 925 600 1300
Maximum 1475 1100 1400 1000 1475 1475 1475 1475
Minimum 1050 750 1050 750 1050 750 525 1050
048 0.75 3/4
Default 1500 1125 1300 975 1500 1125 700 1500
Maximum 1700 1300 1600 1200 1700 1700 1700 1700
Minimum 1200 900 1200 900 1200 900 600 1350
060 0.75 1
Default 1875 1500 1625 1300 1875 1500 875 1875
Maximum 2100 1700 2000 1600 2100 2100 2100 2100
Minimum 1500 1200 1500 1200 1500 1200 750 1500
Air ow is controlled within 5% up to the Max ESP shown with wet coil
Factory shipped on default CFM
BLOWER PERFORMANCE DATA