Step 9. Finishing
Figure 30 shows the minimum vertical and corresponding maximum
horizontal dimensions of fireplace mantels or other combustible
projections above the top front edge of the fireplace. See Figures 4 and
5 for other fireplace clearances. Only non-combustible materials
may be used to cover the black fireplace front.
WARNING: WHEN FINISHING THE FIREPLACE, NEVER
OBSTRUCT OR MODIFY THE AIR INLET/OUTLET GRILLES
IN ANY MANNER.
!
Figure 30.
CAUTION: IF JOINTS BETWEEN THE FIN-
ISHED WALLS AND THE FIREPLACE SUR-
ROUND (TOP AND SIDES) ARE SEALED, A
150°
C. MINIMUM SEALANT MATERIAL
MUST BE USED. THESE JOINTS ARE NOT
REQUIRED TO BE SEALED. ONLY NON-
COMBUSTIBLE MATERIAL (USING 150° C.
MINIMUM ADHESIVE, IF NEEDED) CAN BE
APPLIED AS FACING TO THE FIREPLACE
SURROUND (SEE FIGURE 31).
NOTE: Sheetrock or other combustible
material such as wood can be placed on
the top edge and sides of the fireplace.
Figure 31. Sealant Material
TOP EDGE
SIDE EDGE
TOP EDGE
SIDE EDGE
0” GAP
0” GAP
NOTE: 305mm (12 in.) mantel at
407mm (16 in.) above hood.
102mm
127mm
153mm
178mm
204mm
229mm
254mm
280mm
305mm
51mm
77mm
127mm
153mm
178mm
204mm
228mm
254mm
280mm
305mm
25.4mm
HOOD
331mm
356mm
381mm
407mm
MANTEL
Minimum Vertical and Maximum Horizontal
Dimensions of Combustibles above Fireplace
ST-HVB-CE
PIER-HVB-CE and L&RCOR-HVB-CE
CAUTION: LABEL ALL WIRES PRIOR TO DIS-
CONNECTION WHEN SERVICING CON-
TROLS. WIRING ERRORS CAN CAUSE IM-
PROPER AND DANGEROUS OPERATION.
VERIFY PROPER OPERATION AFTER SER-
VICING.
Step 8. Wiring the Fireplace
NOTE: Electrical wiring must be installed by a licensed electrician.
For Standing Pilot Ignition Wiring
Appliance Requirements
Optional Accessories
Optional remote control kits require that 230 VAC be wired to the facto-
ry installed junction box before the fireplace is permanently installed.
Wall Switch
Position the wall switch in the desired position on a wall. Run a maximum
of 780cm or less length of 0.102 cm diameter minimum wire and connect
it to the fireplace ON/OFF switch pigtails.
!
WARNING: DO NOT CONNECT 230
VAC TO THE GAS CONTROL VALVE
OR THE APPLIANCE WILL MALFUNC-
TION AND THE VALVE WILL BE DE-
STROYED.