Hearth and Home Technologies 4055-187 Indoor Fireplace User Manual


 
Heatilator • Novus NDV Series • 4055-187 Rev. V • 1/1220
D
Clearance to Ceiling
30 in. (762 mm)
0 in.
0 in. TO LEVEL
OF STANDOFFS
Combustible Object
36 in.
(914 mm)
0 in.
Combustible flooring may be installed next
to the front of the appliance.
Drywall
1/2 in.
(13 mm)
1/2 in.
(13 mm)
C
A
B
Model
A
Rough Opening
(Width)
B
Rough Opening
(Height)
C
Rough Opening
(Depth)
D
Rough Opening
(DVP Pipe)
D
Rough Opening
(SLP Pipe)
NDV3630
36 in./914 mm 34-7/8 in./886 mm 19-5/8 in./498 mm 10 in./254 mm 9 in./229 mm
NDV3933
39 in./991 mm 34-7/8 in./886 mm 19-5/8 in./498 mm 10 in./254 mm 9 in./229 mm
NDV4236
42 in./1067 mm 34-7/8 in./886 mm 19-5/8 in./498 mm 10 in./254 mm 9 in./229 mm
NDV4842
48 in./1219 mm 34-7/8 in./886 mm 19-5/8 in./498 mm 10 in./254 mm 9 in./229 mm
B. Constructing the Appliance Chase
A chase is a vertical box-like structure built to enclose the
gas appliance and/or its vent system. In cooler climates the
vent should enclosed inside the chase.
NOTICE: Treatment of ceiling restops and wall shield
restops and construction of the chase may vary with the
type of building. These instructions are not substitutes for the
requirements of local building codes. Therefore, you MUST
check local building codes to determine the requirements
to these steps.
Chases should be constructed in the manner of all outside
walls of the home to prevent cold air drafting problems.
The chase should not break the outside building envelope
in any manner.
Walls, ceiling, base plate and cantilever oor of the chase
should be insulated. Vapor and air in ltration barriers
should be installed in the chase as per regional codes for
the rest of the home. Additionally, in regions where cold
air in ltration may be an issue, the inside surfaces may be
sheetrocked and taped for maximum air tightness.
Figure 5.2 Clearances to Combustibles
C. Clearances
NOTICE: Install appliance on hard metal or wood surfaces
extending full width and depth. DO NOT install directly on
carpeting, vinyl, tile or any combustible material other than
wood.
WARNING! Risk of Fire! Maintain speci ed air space
clearances to appliance and vent pipe:
Insulation and other materials must be secured to prevent
accidental contact.
Failure to maintain airspace may cause overheating and
a re.
To further prevent drafts, the wall shield and ceiling re-
stops should be caulked with caulk with a minimum of 300ºF
continuous exposure rating to seal gaps. Gas line holes
and other openings should be caulked with caulk with a
minimum of 300ºF continuous exposure rating or stuffed with
unfaced insulation. If the appliance is being installed on a
cement slab, a layer of plywood may be placed underneath
to prevent conducting cold up into the room.
Note: If the inside of the framed cavity is to be
nished, the framing dimensions must include the
nished surface.
If drywall is to be attached to the
rear wall, the depth must be measured from the
drywall surface.