Hearth and Home Technologies 2700-I Indoor Fireplace User Manual


 

Page 8
September 1, 2008
R
7007-161H
INSTALLATIONS INTO MOBILE HOMES
Spark Arestor Cap
Roof Flashing
Storm Collar
Joist Shield/Firestop
Double Wall
Connector Pipe

OutsideAir
Cover Box
Back of
Panel
1. An outside air inlet must be provided for combustion and
must remain clear of leaves, debris, ice and/or snow. It
must be unrestricted while unit is in use to prevent room
air starvation which can cause smoke spillage and an
inability to maintain a re. Smoke spillage can also set
off smoke alarms.
2. Unit must be secured to the mobile home structure.

CAUTION
Maintain structural integrity of mobile home:
Floor, wall, ceiling and/or roof.
Do NOT cut through:
Floor joist, wall, studs or ceiling trusses.
Any supporting material that would affect the structural
integrity.
Never install in a sleeping room.
Consumes oxygen in the room.
WARNING
Asphyxiation Risk.
10. Burn wood only. Other types of fuels may generate
poisonous gases (e.g., carbon monoxide).
11. If unit burns poorly while an exhaust blower is on in
home, (i.e., range hood), increase combustion air.
12. Installation shall be in accordance with the Manufacturers
Home & Safety Standard (HUD) CFR 280, Part 24.
1. An outside air inlet must be provided for combustion. See
 for installation information.
2. Appliance must be secured to the mobile home structure
by bolting the pedestal through hearth pad and into
oor.
. Appliance must be grounded with #8 solid copper
grounding wire or equivalent and terminated at each end
with N.E.C. approved grounding device.
4. Appliance must be installed with an approved UL10 HT
ventilated chimney connector, UL10 HT chimney, and
terminal cap with spark arrestor. Never use a single wall
connector (stove pipe) in a mobile home installation. Use
only double-wall connector pipe, Dura-Vent DVL, Selkirk
metalbestos DS or Security DL double-wall connector or
any listed double-wall connector pipe.
5.
In Canada, this appliance must be connected to a 6 inch
(152mm) factory-built chimney conforming to CAN/ULC-
629M, STANDARD FOR FACTORY BUILT CHIMNEYS.
6. Follow the chimney and chimney connector manufacturer’s
instructions when installing the ue system for use in a
mobile home.
7. Maintain clearance to combustibles.
8. Floor protection requirements must be followed
precisely.
9. Use silicone to create an effective vapor barrier at the
location where the chimney or other component penetrates
to the exterior of the structure.
NOTE: Offsets from the vertical, not exceeding 45°, are
allowed per Section 905(a) of the Uniform Mechanical Code
(UMC). Offsets greater than 45° are considered horizontal
and are also allowed, providing the horizontal run does not
exceed 75% of the vertical height of the vent. Construction,
clearance and termination must be in compliance with the
UMC Table 9C. This installation must also comply with NFPA
211.
NOTE: Top sections of chimney must be removable to allow
maximum clearance of 1.5 feet (411cm) from ground level
for transportation purposes.
WARNING
Do not draw outside combustion air from:
Wall, oor or ceiling cavity
Enclosed space such as an attic or garage
Close proximity to exhaust vents or chimneys.
Fumes or odor may result
Fire Risk.
Asphyxiation Risk.