Hearth and Home Technologies 2700-I Indoor Fireplace User Manual


 
Page 5
September 1, 2008
R
7007-161H

AVOID FIRE: To ensure that insulation or any other combustible
material does not contact the chimney, a chimney inside the house
must have at least 2 inches (51mm) of air space clearance around
t
he chimney. A chimney outside the house must have at least 1
inch (25mm) clearance to the combustible structure. Non-combus-
tible re stops must be installed at the spaces where the chimney
passes through oors and/or ceilings. 
  Canadian installations require a full reline of the
chimney.
CHIMNEY HEIGHT/DRAFT
To be sure that your Quadra-Fire insert burns properly, the chimney
draft (static pressure) should be approximately -0.10 inches water
column (W.C.) during a high burn and -0.04 inches W.C. during a
low burn, measured 6 inches (152mm) above the top of the insert
after one hour of operation at each burn setting.
NOTE: These are guidelines only, and may vary somewhat for
individual installations.
Your Quadra-Fire insert was designed for and tested on a 6 inch
(152mm) chimney, 12 ft-14 ft (60-420cm) high, measured from
the base of the insert. In addition, exterior conditions such as
roof line, surrounding trees, prevailing winds and nearby hills can
inuence insert’s performance. Your local dealer is the expert in
your geographic area and can usually make suggestions or discover
solutions that will easily correct your ue problem.
A masonry chimney or a listed factory-built UL10 HT Class “A”
chimney must be the required height above the roof and any other
nearby obstructions. The chimney must be at least  ft (91cm) higher
than the highest point where it passes through the roof and at least
2 ft (61cm) higher than the highest part of the roof or structure that
is within 10 ft (05cm) of the chimney, measured horizontally. See
 These are safety requirements and

 ft Min
(91cm)
2 ft Min (61cm)
10 ft Min
(05cm)


NOTE: Clearances may only be reduced by means approved by

     
insurance company representative review your plans before
installation.
INSTALLATION RECOMMENDATIONS
The Quadra-Fire 2700-I Insert has met and surpassed the most
stringent emissions standards in the United States. The sophistica-
tion of the interior rebox design requires that a proper draft be sup-
plied by the chimney, therefore adherence to the following factors
will enable your insert to operate at its optimum capability.
REQUIRED: Direct connection to the rst ue liner in accordance
with the requirements of the NFPA 211. In USA a full chimney
liner for factory-built replaces is recommended but is required in
Canada.
BEST: A complete relining of the chimney system with a 6 inch
(152mm) diameter listed, stainless liner. Required for factory-built
replace installations in Canada, recommended in USA. The sections
must be attached to the insert and to each other with the crimped
(male) end pointing toward the insert. See . All joints,
including the connection at the ue collar, should be secured with
three sheet metal screws. Make sure to follow the minimum clear-
ances to combustibles as set out on  of the manual.
These installation instructions describe the installation and opera-
tion of the Quadra-Fire 2700-I Wood Insert. This insert meets the
U.S. Environmental Protection Agency’s 1990 particulate emission
standards. The 2700-I is listed by OMNI-Test Laboratories, Inc.
(Report No. 061-S-52-2), to UL Safety Standard 1482, and ULC
S628-9, and (UM) 84-HUD. The 2700-I is approved for mobile
home installations when not installed in a sleeping room and when
an outside combustion air inlet is provided. The structural integrity
of the mobile home oor, ceiling, and walls must be maintained.
The insert must be properly grounded to the frame of the mobile
home.
Check with your local building code agency before you begin your
installation to ensure compliance with local codes, including the
need for permits and follow-up inspections. Be sure local building
codes do not supersede UL specications. Always obtain a building
permit so that insurance protection benets cannot be unexpectedly
cancelled. If any assistance is required during installation, please
contact your local dealer.
LISTINGS CHIMNEY HEIGHT/DRAFT

Fire Risk.
Comply with all minimum clearances to
combustibles as specied.
Failure to comply may cause house re.
WARNING
LINER CONNECTOR
FLUE
GAS
DIRECTION
CRIMPED
END
TOWARDS
STOVE