Hearth and Home Technologies 2700-I Indoor Fireplace User Manual


 
Page 7
September 1, 2008
R
7007-161H

Floor
Ceiling
Caulk
Floor
(second Story)
Non-Combustible
Firestopping
Material

clearance from exterior


2 inch
(51mm)
CHIMNEY REQUIREMENTS
Non-combustible


from combustible material
and insulation
ceilin
At least 2 ft
(61cm)
At least  ft
(91cm)
CHIMNEY HEIGHT
10 ft
(05cm)
CHIMNEY TOP VIEW
FLUE
Foundation
1/2" (12.7mm) airspace
5/8" (16mm)
Fireclay Flue
Liner
Chimney Wall
4" (102mm)
Nominal

OVALIZING ROUND STAINLESS STEEL
LINERS
Ovalizing round stainless steel liners to accommodate the
liner passing through the damper region of a replace is an
allowable and acceptable practice.
Ensure that the ovalization is minimized to the extent
required to t through the damper.



WARNING
ONLY use connector:
Within the room, between appliance and ceiling or wall.
Connector shall NOT pass through:
Attic or roof space
Closet or similar concealed space
Floor or ceiling
Maintain minimum clearances to combustibles
Fire Risk.
Follow Chimney Connector Manufacturer’s
Instructions for Proper Installation.
WARNING
ALWAYS maintain specied clearances around venting and
spacers.
Install spacers as specied.
Failure to keep insulation or other material away from vent
pipe may cause re.
Fire Risk.
Do NOT pack insulation or other combustibles
between spacers.