INSTALLATION IN CANADA
MASONRY and HEAT-CIRCULATING
(INSTALLATIONS INTO FACTORY-BUILT FIREPLACES ARE
PROHIBITED IN CANADA)
Whether installed in a masonry or heat-circulating re-
place, this replace insert must be installed with a continu-
ous chimney liner of 6 inches (152mm) diameter extending
from the replace insert to the top of the chimney. The
chimney liner must conform to the Class requirements
of CAN/ULC-S65, Standard for Lining Systems for Exist-
ing Masonry or Factory-Built Chimneys and Vents, or CAN/
ULC-S640, Standard for Lining Systems for New Masonry
Chimneys.
         
accommodate insert.






 
may have been altered to accommodate the insert, and
-

LEVELING LEGS
Remove
screw
s
1. Remove the 2 screws already installed on each leg.
2. Move legs to the desired height.
. Re-install the screws to secure in place.

DOOR HANDLE ASSEMBLY
1. Install washer on door handle shaft.
2. Slide door handle through door.
. Install second washer(s) as shown.
4. Install key in groove.
5. Align groove in latch cam with key; slide latch cam over
shaft.
6. Install locknut.
7. Install spring handle turning counter-clockwise to
desired location on handle.
Locknut
Door Cross Section
(example)
Latch Cam
Spacing
Washers
Square Key
Door Handle
Spring
Handle

NOTE:
In Canada when using a factory-built chimney it must be
safety listed, Type UL 10 HT CLASS "A" or conforming
to CAN/ULC-S629, STANDARD FOR 650°C FACTORY-
BUILT CHIMNEYS.
CAUTION
Do NOT overtighten lock nut.
Door handle needs to move smoothly.