DGX Industrial Space Heating
Installation of Diffuser and Remote
Panel (TSCP)
NOTE
The location of the discharge diffuser and the TSCP
Space Heat Remote Panel are critical for optimum
performance of the Greenheat™ System.
2. Install TSCP
When installing the TSCP Space Heat Remote
Panel, the location is critical to performance of the
Greenheat™ System. The TSCP should be installed five
to six feet above the floor. It is recommended that the
TSCP be installed on an outside wall, in the space, and
close to any source of infiltration such as dock doors.
DO NOT install the TSCP in the blast area of the heater
or near any other source of heat.
Indoor Mounted
Unit
h
h
Thru-Wall Diffuser Height
Rooftop
Unit
h
h
Rooftop Diffuser Height
hh
Blast Area
Recommended
TSCP Location
TSCP Location
IMPORTANT
DO NOT install the TSCP in the blast area of the
space heater or near any other source of heat.
Airflow
(cfm)
Diffuser Height (feet)
Minimum Recommended Maximum
4000 15 20 25
6000 15 20 25
8000 20 20-25 30
10000 20 25-30 35
13000 -
20000
25 30-35 40
1. Install Diffuser
Using self-tapping screws, attach diffuser to the
ductwork or unit. Be sure to maintain the recommended
floor to diffuser height. Refer to the chart for the
recommended diffuser height.
®