Greenheck Fan Part #470655 Electric Heater User Manual


 
21
DGX Industrial Space Heating
Heater Does Not Operate
Does not attempt to light (No visible spark)
Troubleshooting
24VACbetween
terminals W1 and X?
Heat Switch (S4) Off
(Turn Heat Switch (S4) On)
Heat Switch Not Wired
(Wire Heat Switch (S4))
115VACbetween
terminals 102 and 101?
Primary Fuses Blown
(Replace Fuses)
Main Transformer (TR4) Defective
(Replace Transformer)
115VACbetween
terminals 106 and 101?
(Optional) High/Low Gas Pressure Switch(es)
(PS3 and PS4) Tripped
(Correct gas pressure and reset)
(Reference Direct Gas Start-Up – Steps #2 and #3)
115VACbetween
terminals 104 and 101?
High Limit (HLC1) Tripped
(Reset/Replace High Limit (HLC1))
(Check on cause of control loss)
Continuity between
terminals 107 and 108?
115VACbetween
terminals 103 and 101?
(Optional) Inlet Air Sensor (TS4) Holding
(Adjust TS4 setting. Reference Blower Start-Up – Step #6)
Heat Relay (RH) Defective
(Replace Heat Relay (RH))
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Airflow Switch (PS2) Holding for Proper Airflow
(Correct airflow across burner)
(Reference Direct Gas Start-Up – Step #4a or 4b)
Yes
The power light on the flame safeguard should
blink approximately every 5 seconds as it
performs a self-diagnostics check.
At this time the heater should attempt to light.
(The pilot light on the flame safeguard should illuminate).
®