Greenheck Fan Part #470655 Electric Heater User Manual


 
17
DGX Industrial Space Heating
Proper supply power at
main disconnect
Check Main Voltage
(See Blower Start-Up – Step #1)
Main Disconnect (DS1) Off
(Turn Main Disconnect DS1 On)
Primary Fuses Blown
(Replace Fuses)
24VACbetween
terminals R and X?
Main Transformer (TR1) Defective
(Replace Transformer)
24VACbetween
terminals G and X?
Supply Switch (S2) Off
(Turn Supply Switch (S2) On)
Fire system contact (FSC) tripped/not installed
(Correct/Replace)
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Blower Does Not Operate
Broken Fan Belt
(Replace - reference V-Belt Drives in the Maintenance section)
Defective motor or capacitor
(Repair/Replace)
Blown Motor Fuse
(Replace)
One or more legs of 3 phase is out
(Restore missing legs)
24VACacrossA2andA1on
supply contactor (ST1)
24VACacross
terminals 4 and X?
24VACacross
terminals 3 and X?
Supply Fan Overload (ST1 OL) Tripped
(Reset and check motor amps, reference Blower Start-Up – Step #4)
Optional Exhaust Fan Interlocks (ST2-ST5) Open
(Correct/Replace)
(Optional) Damper Limit Switch (DL1) Holding
(Wait for actuator to open fully or adjust limit switch)
(Optional) Damper Limit Switch Jumper Missing
(Install jumper, reference the unit’s ladder diagram for terminals)
Fan Relay (RF) is not energized
(Check for loose connection; repair or replace relay)
(Optional) Freeze Protection (RT4) Tripped
(Reset)
Troubleshooting
At this time the supply contactor (ST1) should
pull in, passing power to the supply motor
and the blower should start.
®