16
DGX Industrial Space Heating
Operation - Electrical Sequence
With 7-Day Timer
1. Switch (S2) in Summer Mode
• PowerpassesthroughN.C.eld-suppliedre
contact (FSC)
• PowerpassesthroughterminalG
• PowerpassesthroughN.C.contactonsupply
starter overload (ST1 OL), which is closed if the
supply fan has not overloaded
• PowerpassesthroughN.Ccontactonoptional
freeze protection timer (RT4), which is closed if the
temperature has remained above the set point.
• Powerpassestoandenergizesoptionalinlet
damper (D1), which opens
• Powerpassestoandenergizesfanrelay(RF)
• PowerpassestoN.O.contactonfanrelay(RF),
which closes once the fan relay (RF) is activated
• Powerpassestoandenergizessupplyfanstarter
(ST1)
• N.O.contactonsupplyfanstarter(ST1)is
energized and closed
• Supplyfan(M1)starts
2. Switch (S2) in Winter Mode
• Ifspacetemperatureislessthanthedaytime
temperature setting, the N.O. contact on the
temperature sensor (TS1) closes and power passes
to the timer (TC1). If the timer (TC1) is on, power
passes through N.C. field-supplied fire contact
(FSC). If the timer (TC1) is off, but the space
temperature is less than the nighttime temperature
setting, the N.O. contact on the temperature sensor
(TS2) closes and power passes through N.C. field-
supplied fire contact (FSC)
• PowerpassesthroughterminalW1andthen
energizes the space heat relay (RS)
• PowerpassesthroughN.O.contactonthespace
heat relay (RS), which is energized and closed
• PowerpassesthroughterminalG
• PowerpassesthroughN.C.contactonsupply
starter overload (ST1 OL), which is closed if the
supply fan has not overloaded
• PowerpassesthroughN.C.contactonoptional
freeze protection timer (RT4), which is closed if the
temperature has remained above the set point
• Powerpassestoandenergizesoptionalinlet
damper (D1), which opens
• Powerpassestoandenergizesfanrelay(RF)
• PowerpassestoN.O.contactonfanrelay(RF),
which closes once the fan relay (RF) is activated
• Powerpassestoandenergizessupplyfanstarter
(ST1)
• N.O.contactonsupplyfanstarter(ST1)is
energized and closed
• Supplyfan(M1)starts
• PowerpassesthroughN.O.contactonfanrelay
(RF), which is energized and closed
• Powerpassestoandenergizestheheatrelay(RH)
• PowerpassesthroughN.O.contactonheatrelay
(RH), which is energized and closed
• Powerpassestoandenergizesterminal5onthe
Flame Safeguard (FSG)
• PowerpassesthroughN.C.contactonhigh
temperature limit control (HLC1), which remains
closed if the temperature has remained below the
HLC1 set point
• PowerpassesthroughoptionalN.C.andN.O.high
and low gas pressure contacts (PS4 and PS3),
which are both closed if the gas pressure is within
the set range
• Powerpassestoterminal6ontheFlameSafeguard
(FSG)
• FlameSafeguard(FSG)beginsdirectgasburner
sequence (See Flame Safeguard Sequence)
3. Flame Safeguard (FSG) Sequence
• Veriesproperairowwithairowswitch(PS2)
• Veriesnoameispresentatburner
• Initiates10secondprepurge
• Sendspowertoopenpilotvalve(V1)andenergizes
the spark generator (SG) (clicking of the spark
generator may be heard)
• Energizessparkgeneratorforupto10secondsto
light pilot and confirm flame
• Powersthemaingasvalve(V2)open
• Shutsdownsparkgenerator(SG)
• Continuouslymonitorstheameandairow
• Performsself-diagnosticcheckeveryfourseconds
®