Greenheck Fan Part #470655 Electric Heater User Manual


 
14
DGX Industrial Space Heating
10. Program the 7 Day Time Clock
Follow the detailed Programming and Operating
Instructions for 7 Day Time Clock that shipped with
the unit. Set the timer ON times to the times when the
daytime temperature setting is to be used. Set the timer
OFF times to the times when the nighttime temperature
setting is to be used.
11. Flame Signal Check
To measure the flame signal connect a standard DC
voltmeter to the flame amplifier test jacks + and - (com)
as shown. The flame signal should be above 1.25 VDC
and steady.
Check the flame signal with the burner at pilot only,
minimum fire, mid-fire and high-fire.
9. Set Nighttime Temperature
Set the nighttime temperature setting to the desired
nighttime space temperature, the nighttime temperature
setting is located inside the TSCP Space Heat remote
panel which should be mounted in the space. The TSCP
Space Heat remote panel controls image is found on
page 13.
Flame Signal Check
NOTE
For the unit to function properly, the daytime
temperature setting should always be set higher than
the nighttime temperature.
NOTE
If the flame signal is not above 1.25 VDC and steady,
consult the Troubleshooting section.
NOTE
For units without a 7 day time clock, skip Steps #9
and #10.
Start-Up Direct Gas continued
®