Goodman Mfg CPG SERIES Heating System User Manual


 
26
APPENDIX A BLOWER PERFORMANCE DATA
BELT DRIVE - HIGH STATIC (“AA” MODELS ONLY)
NOTE: High Static airflow requires installation of High Static Kit (HSKT*), or factory-built High Static model. Unit factory shipped at 2.5 turns open.
Tables represent dry coil without filter. To compensate for filter, add 0.08" to measured E.S.P. SCFM correction for wet coil = 4%.
CPG090 HIGH STATIC BELT DRIVE DOWN SHOT
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
0.7
3575 904 1.66
0.9
3258 925 1.56 3113 909 1.41
1.1
3580 1013 1.97 3001 948 1.42 2722 915 1.25
1.3
3616 1063 2.17 3247 1019 1.79 2646 959 1.3
1.5
3275 1069 2.05 2803 1025 1.68
1.7
3346 1118 2.24 2885 1074 1.97
1.9
3009 1125 2.05
2.1
CPG120 HIGH STATIC BELT DRIVE DOWN SHOT
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
0.8
4188 943 2.11 3793 889 1.67
1
4305 1002 2.39 3836 946 1.89 3416 893 1.45
1.2
4324 1053 2.63 3879 1003 2.11 3425 951 1.63
1.4
4428 1109 2.92 3973 1056 2.35 3434 1009 1.8
1.6
4465 1160 3.2 4088 1113 2.67 3506 1068 2.1
1.8
4129 1168 2.9 3625 1122 2.3
2
3694 1175 2.65
CPG090 HIGH STATIC BELT DRIVE HORIZONTAL
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
0.7
3567 903 1.58
0.9
3596 953 1.79 3145 906 1.39
1.1
3630 1007 1.97 3168 963 1.56 2675 909 1.18
1.3
3649 1063 2.19 3255 1021 1.8 2724 965 1.35
1.5
3316 1068 2 2823 1058 1.61
1.7
3287 1112 2.16 2869 1074 1.78
1.9
2970 1122 2
2.1
2644 1133 1.92
CPG120 HIGH STATIC BELT DRIVE HORIZONTAL
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
0.8
4408 885 2.02
1
4464 940 2.29 3929 891 1.76
1.2
4585 996 2.58 4026 946 2 3436 897 1.46
1.4
4697 1049 2.92 4141 1001 2.26 3509 951 1.7
1.6
4264 1056 2.58 3663 1007 1.96
1.8
4359 1105 2.85 3785 1061 2.22
2
3907 1114 2.49
DO NOT
OPERATE
ESP, In
H
2
O
TURNS OPEN
012345
ESP, In
H
2
O
TURNS OPEN
012345
ESP, In
H
2
O
TURNS OPEN
012345
DO NOT
OPERATE
DO NOT
OPERATE
TURNS OPEN
ESP, In
H
2
O
450123
CPG150 HIGH STATIC BELT DRIVE HORIZONTAL
ESP (IN
W.C.) CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.6 5967 3.92 5451 3.16 5275 2.77
0.8 5628 3.61 5223 2.97 4959 2.54
1.0 5840 4.10 5385 3.39 4999 2.80 4635 2.31
1.2 5643 3.90 5003 3.06 4803 2.65 4160 1.99
1.4 60074.9357404.3252293.5145762.7144402.38
1.6 5752 4.64 5401 3.97 4917 3.23
1.8 5380 4.24 5033 3.61 4397 2.79
2.0 5065 3.91 4573 3.18
CPG150 HIGH STATIC BELT DRIVE DOWN SHO
T
ESP (IN
W.C.)
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.6 5515 3.21 5124 2.68
0.8 5840 4.06 5781 3.73 5344 3.07 4721 2.37
1.0 59084.4956433.8653693.3648872.7143652.13
1.2 5869 4.74 5542 4.11 5229 3.47 4853 2.92 4404 2.35 3986 1.88
1.4 54644.3051803.7549173.1945842.7141972.21
1.6 52294.0549603.5343972.7542042.41
1.8 4961 3.78 4553 3.16
2.0 4790 3.61 4315 2.95
0 TURNS 1 TURN 2 TURNS 3 TURNS
4 TURNS 5 TURNS
4 TURNS 5 TURNS
0 TURNS 1 TURN 2 TURNS 3 TURNS