CPG090 STANDARD BELT DRIVE HORIZONTAL
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
0.1
3381 703 0.99 3078 659 0.78
0.3
3560 796 1.26 3271 747 1.02 2946 703 0.82 2604 659 0.63
0.5
3492 841 1.36 3159 799 1.09 2819 752 0.86
0.7
3453 891 1.5 3094 846 1.18
0.9
2964 896 1.29 2524 852 0.96
1.1
2537 902 1.08
CPG102 STANDARD BELT DRIVE HORIZONTAL
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
0.1
3231 700 0.96 2928 656 0.75
0.3
3410 793 1.23 3121 744 0.99 2796 700 0.79
0.5
3342 838 1.33 3009 796 1.06 2669 749 0.83
0.7
3303 888 1.47 2944 843 1.15
0.9
2814 893 1.26
CPG120 STANDARD BELT DRIVE HORIZONTAL
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
0.2
4391 737 1.48 4054 693 1.22 3760 645 0.97
0.4
4314 781 1.61 3969 737 1.29 3534 693 1
0.6
4255 826 1.69 3894 781 1.38 3447 743 1.09
0.8
4234 876 1.85 3792 832 1.47
1
3724 877 1.59
1.2
ESP, In
H
2
O
TURNS OPEN
012345
ESP, In
H
2
O
TURNS OPEN
012345
ESP, In
H
2
O
TURNS OPEN
012345
CPG150 STANDARD BELT DRIVE HORIZONTAL
ESP (IN
W.C.)
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.2 57623.0854852.6351402.2148551.8445131.4841971.20
0.4 55502.9152072.4448572.0344891.6441001.29
0.6 52022.6549222.2544871.8141131.45
0.8 48982.4345151.9940741.58
1.0 4549 2.20 4135 1.76
1.2 4258 2.01
0 TURNS 1 TURN 2 TURNS 3 TURNS 4 TURNS 5 TURNS