Goodman Mfg CPC/CPH Air Conditioner User Manual


 
23
APPENDIX A BLOWER PERFORMANCE TABLES
BELT DRIVE
STANDARD HORIZONTAL
CPC/H036 STANDARD BELT DRIVE HORIZONTAL
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.2
1658 0.35 1489 0.28
0.4
1560 0.36 1339 0.28 1129 0.21
0.6
1682 0.47 1436 0.36 1196 0.27 949 0.19
0.8
1581 0.50 1354 0.38 1096 0.28 828 0.18
1.0
1266 0.39 994 0.28 756 0.19
1.2
923 0.28
CPC/H048 STANDARD BELT DRIVE HORIZONTAL
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.2
1943 0.52 1714 0.40
0.4
21870.7218760.5515660.4012700.26
0.6
2044 0.72 1761 0.56 1444 0.40 1136 0.26
0.8
1947 0.74 1704 0.59 1335 0.40
1.0
1598 0.60 1275 0.36
1.1
1208 0.45
CPC/H060 STANDARD BELT DRIVE HORIZONTAL
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.2
2420 0.79 2198 0.64
0.4
26051.0223580.8421330.6718740.52
0.6
2526 1.06 2300 0.88 2026 0.70 1806 0.55
0.8
2529 1.15 2252 0.93 1975 0.73 1670 0.54
1.0
2233 0.99 1943 0.78 1628 0.57
1.2
1907 0.83 1582 0.61
CPC/H072 STANDARD BELT DRIVE HORIZONTAL
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.2
2784 1.30 2582 0.83 2411 0.79
0.4
28141.3426201.1923420.7221050.66
0.6
26651.3425831.1923981.0621030.6219020.57
0.8
2689 1.38 2492 1.22 2370 1.07 2142 0.91 1816 0.51
1.0
2438 1.22 2275 1.09 2098 0.92 1883 0.78
1.2
2250 1.10 1996 0.92
NOTES:
ESP, In
H
2
O
TURNS OPEN
012345
Tables represent dry coil without filter, to compensate for filter add 0.08" to measured E.S.P.
SCFM correction for wet coil = 4 %.
ESP, In
H
2
O
TURNS OPEN
012345
ESP, In
H
2
O
TURNS OPEN
012345
ESP, In
H
2
O
TURNS OPEN
012345