EMI S1C Heat Pump User Manual


 
www.enviromaster.com
WLCA/WLHA High Wall Evaporator
36
WLCA/WLHA HIGH WALL
EVAPORATOR SPECIFICATIONS
DISCHARGE AIR SPEED AND FLOW @ 230V
Model
High
CFM
Low
CFM
Coil FPM
Throw/
Ft.
09/12 400 350 Dry 900 15
18/24 750 675 Dry 1,225 25
30/36 1,100 900 Dry 1,250 27
WLCA/WLHA
INTERCONNECTING-LINE SIZE
System
Capacity
Btuh
Liquid
O.D.
Suction
O.D.
Condensate
I.D.
09 1/4” 1/2” 1/2”
12 1/4” 1/2” 1/2”
18 3/8” 5/8” * 1/2”
24 3/8” 3/4” 1/2”
30 3/8” 3/4” ** 1/2”
36 3/8” 3/4” ** 1/2”
* WLCA/WLHA Suction Connection size is 3/4” O.D.
and must bush down at the WLCA/WLHA Unit.
** WLCA Suction Connection size is 5/8” O.D. a
factory supplied kit is provided to transition to 3/4”
O.D. interconnect.
WLCA/WLHA ELECTRICAL SPECIFICATIONS
MODEL
#
VOLTS/HZ/PH
FAN
RLA
HP
HEATER
K.W.
AMPS
TOTAL
AMPS
MIN
VOLT
M.C.A.
HACR
BRKR
SMALL CABINET 09/12
09/12
115/60/1 0.64 0.02 0.64 104 0.8 15
115/60/1 0.64 0.02 0.75 6.50 7.14 104 8.9 15
208/230/60/1 0.34 0.02 0.34 197 0.4 15
208/230/60/1 0.34 0.02 3.00 13.04 13.38 197 16.7 20
MEDIUM CABINET 18/24
24
115/60/1 1.20 0.083 1.20 104 1.5 15
115/60/1 1.20 0.083 0.75 6.52 7.72 104 9.7 15
115/60/1 1.20 0.083 1.25 10.90 12.10 104 15.1 20
208/230/60/1 0.56 0.070 0.56 197 0.7 15
208/230/60/1 0.56 0.070 3.00 13.04 13.60 197 17.0 20
208/230/60/1 0.56 0.070 5.00 21.74 22.30 197 27.9 30
LARGE CABINET 30/36
30/36
208/230/60/1 0.80 1/10 0.80 197 1.0 15
208/230/60/1 0.80 1/10 5.00 21.74 22.54 197 28.2 30