System and Control Options
34
6.7.1 View Last Map
The View Last Map option allows you to review the mapped points
from the last mapping of a zone. This feature is the data logger for the
mapmode process described in the previous section, 6.7 - Setup Sys-
tem - Setup Mapmode.
In the View Last Map mode, the Liqui-tect panel shows the mapped
distance to a particular point along the leak detection cable, identify-
ing each point with an entry number that corresponds to point “X”
(where X represents 1 for the first point, 2 for the second, and so on).
The user may view the entry number for point “X” and see the corre-
sponding distance to that point. This may be used either to record that
distance on the floor map or to verify the distance already recorded on
the map.
When a leak occurs, the Liqui-tect Monitoring System displays the
distance of the leak. By referring to the final floor map, you can easily
determine the location of the leak.
To view the last map:
• From the Setup System Menu, shown at right, use the arrows
↑↓
to
choose Setup Mapmode and press Enter ↵.
• Use the arrows
↑↓ to choose View Last Map from the Select Zone
to Map Menu, and press Enter ↵.
(If no points have been mapped, the screen displays a message, as
shown below right.)
• If you haven’t already done so, record the distance for each point
on the final floor map next to the respective positions of each short
labeled “X” (for points 1, 2, 3 and so on as described in step 3 in the
previous section).
• Use the arrows
↑↓ to display the mapping data for the next point.
• When finished, press Enter ↵.
Setup System Menu
SETUP ZN1 ZONE 1
SETUP ZN2 ZONE 2
SETUP ALARM OUTPUTS
↑↓=NEXT ↵=SELECT
SETUP REALARM DELAY
> SETUP MAPMODE
SETUP SYSTEM INFO
Select Zone to Map
SELECT ZONE TO MAP
ZN1 ZONE 1
ZN2 ZONE 2
↑↓=NEXT ↵=SELECT
> VIEW LAST MAP
Mapping for Last Map
MAPPING FOR LAST MAP
CURRENT: 0UA
DISTANCE: ----
ENTRIES:0 ESC=EXIT
Message if No Mapping
THERE ARE NO
MAPPED POINTS
LOGGED
ESC=EXIT