6.4 Setup System - Setup ZN2 Zone 2
The Liqui-tect panel has two independent zones—ZN1 and ZN2—that
may be configured individually. Each zone can monitor up to 5,000 ft.
(1524m) of leak detection cable.
To configure the second zone:
In the Setup System Menu, choose Setup ZN2 Zone 2 (see above
right).
Follow the same procedures used in setting up Zone 1, as
described in the previous section, 6.3 - Setup System - Setup
ZN1 Zone 1.
NOTE
The setup options are identical for both zones, except the
name of the zone differs.
Setup System Menu
SETUP ZN1 ZONE 1
> SETUP ZN2 ZONE 2
SETUP ALARM OUTPUTS
↑↓=NEXT =SELECT
SETUP REALARM DELAY
SETUP MAPMODE
SETUP SYSTEM INFO
Setup Zone 2 Menu
SETUP ZN2 ZONE 2
> CONNECTED: N
LABEL: ZONE 2
↑↓=NEXT =SELECT
UNITS: FT
AUTO CALIBRATE
WATER DETECT:150 UA
CONTAMINATED:050 UA