Emerson MC68HC16Z1 Home Security System User Manual


 
Installation
10
2.4 Connect Power to the Liqui-tect Panel
The Liqui-tect panel requires 24VAC for proper operation. Liebert recommends using the optional
Transformer Module manufactured by Liebert or another UL-approved Class 2 power unit to obtain
proper voltage. If the power unit is not a Class 2 circuit, it must be protected with an IEC 5 x 20mm
time lag 2A fuse. For information, consult your local dealer, Liebert representative or the Liebert
Worldwide Support Group.
2.4.1 Input Power Connections - Small Enclosure
To connect electrical power:
1. Run conduit and electrical wiring from building to the Liqui-tect panel.
2. Use copper wires only; proper wiring to use for 24VAC power is 18-22 AWG stranded and shielded
(18 AWG is recommended—see Table 4). Strip wires 1/2".
Figure 5 Electrical connections to panel
3. Secure the incoming electrical service wires to the Liqui-tect panel’s 24VAC input by sliding the
wires into TB1, the 24VAC input terminal block. There is no polarity requirement when
connecting to TB1. The ground wire must be connected to the earth ground terminal located on
the side of the panel (see Figure 5).
!
WARNING
Check that power is removed from wires prior to installation.
!
CAUTION
The Liqui-tect panel is designed for use on properly grounded (earthed) 24VAC power, 50Hz
or 60Hz. The ground wire for the power lead must be wired to the earth ground terminal (stud
located next to the 24VAC terminal block).
This equipment is intended to be installed by a qualified and certified electrician who must
review and approve customer supplied wiring and circuit breakers, verify correct input and
grounded (earthed) connections to ensure compliance with technical standards and national
and local electrical codes.
!
WARNING
Be sure that the power wiring is disconnected from the Liqui-tect panel before installing any
wiring to this unit.
SW3
EGND1
TVS3
TB1
FB2
R4
24V Power
Reset
24VAC input
connector
24VAC wiring
(red & white)
External wiring
through knockout
Earth ground
terminal
Ground wire
(black)