Desa VMH26NRB Indoor Fireplace User Manual


 
www.desatech.com 113110-01A
18
4. Check all gas connections for leaks. See
Checking Gas Connections.
5. Replace branch support back into fireplace.
Feed flexible gas line into fireplace base area
while replacing branch support. Make sure the
entire flexible gas line is in fireplace base area.
Reattach branch support to fireplace with
screws removed in step 1, page 17.
INSTALLATION
Continued
Figure 23 - Attaching Flexible Gas Line
to Equipment Shutoff Valve
Flexible Gas Line
from Fireplace Gas
Regulator Provided
With Fireplace
To Control
Valve
Equipment
Shutoff Valve
PROPANE/LP
To External
Regulator
NATURAL
To Gas Supply
CHECKING GAS CONNECTIONS
WARNING: Test all gas pip-
ing and connections, internal
and external to unit, for leaks
after installing or servicing. Cor-
rect all leaks at once.
WARNING: Never use an
open flame to check for a leak.
Apply a noncorrosive leak de-
tection fluid to all joints. Bubbles
forming show a leak. Correct all
leaks at once.
CAUTION: Make sure exter-
nal regulator has been installed
between propane/LP supply and
fireplace. See guidelines under
Connecting to Gas Supply
,
pages 16 and 17.
Pressure Testing gas Supply Piping
System
Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)
1. Disconnect appliance with its appliance main
gas valve (control valve) and equipment
shutoff valve from gas supply piping system.
Pressures in excess of 1/2 psig will damage
heater regulator.
2. Cap off open end of gas pipe where equip-
ment shutoff valve was connected.
3. Pressurize supply piping system by either
opening propane/LP supply tank valve for
propane/LP gas or opening main gas valve lo-
cated on or near gas meter for natural gas, or
using compressed air.
4. Check all joints of gas supply piping system.
Apply noncorrosive leak detection fluid to all
joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Reconnect fireplace and equipment shutoff
valve to gas supply. Check reconnected fit-
tings for leaks.
Test Pressures Equal To or Less Than 1/2 PSIG
(3.5 kPa)
1. Close equipment shutoff valve (see Figure 24).
2. Pressurize supply piping system by either
opening propane/LP supply tank valve for
propane/LP gas or opening main gas valve lo-
cated on or near gas meter for natural gas, or
using compressed air.
3. Check all joints from gas meter to equipment
shutoff valve for natural gas or propane/LP
supply to equipment shutoff valve for propane/
LP (see Figures 25 or 26, page 19). Apply non-
corrosive leak detection fluid to all joints.
Bubbles forming show a leak.
4. Correct all leaks at once.
Figure 24 - Equipment Shutoff Valve
ON
POSITION
OFF
POSITION
Open
Closed
Equipment
Shutoff Valve