43
IX System Piping
A. General System Piping Precautions
CAUTION
THE HEAT EXCHANGER USED IN THE BWC IS MADE FROM A SPECIAL ALUMINUM ALLOY.
FAILURE TO TAKE THE FOLLOWING PRECAUTIONS COULD RESULT IN SEVERE BOILER
DAMAGE.
BEFORE CONNECTING BOILER, MAKE SURE THAT THE SYSTEM IS FREE OF SEDIMENT,
FLUX AND ANY RESIDUAL BOILER WATER ADDITIVES. FLUSH THE SYSTEM IF
NECESSARY TO ENSURE THAT THESE CONTAMINATES ARE REMOVED.
DO NOT CONNECT THIS BOILER TO A SYSTEM THAT IS SUBJECT TO REGULAR ADDITIONS
OF MAKEUP WATER OR ONE WHICH EMPLOYS RADIANT TUBING WITHOUT AN OXYGEN
BARRIER.
DO NOT ADD ANTIFREEZE OR OTHER BOILER WATER TREATMENT CHEMICALS EXCEPT
THOSE LISTED IN PART XI OF THIS MANUAL.
MAINTAIN THE PRESSURE IN THE BOILER AT A MINIMUM OF 12 PSI.
DESIGN SYSTEM TO ENSURE THAT THE FLOW FALLS WITHIN THE LIMITS CALLED FOR IN
TABLE 9.1.
B. System Design
Proper operation of the BWC boiler requires that the water ow through the boiler remain within the limits shown in
Table 9.1 any time the burner is ring. Failure to maintain the ow within these limits could result in erratic operation or
premature boiler failure.
There are two basic methods that can be used to pipe the BWC boiler. Method #1 is almost always preferred. The
instructions on the following pages describe these methods for piping BWC boilers and explain how to size the circulator
and piping. Additional information on hydronic system design may be found in Installation of Residential Hydronic
Systems (Pub. #200) published by the Hydronics Institute in Berkeley Heights, NJ.
TABLE 9.1: FLOW REQUIREMENTS THROUGH BOILER
BOILER MODEL
MIN. REQUIRED FLOW
(GPM)
MAX. ALLOWABLE
FLOW (GPM)
BWC070 4.0 9.0
BWC090 4.0 9.0
BWC120 4.5 12.0
BWC151 6.0 15.0
WARNING
INSTALL BOILER SO THAT THE GAS IGNITION SYSTEM COMPONENTS ARE PROTECTED
FROM WATER (DRIPPING, SPRAYING, RAIN, ETC) DURING APPLIANCE OPERATION AND
SERVICE (CIRCULATOR REPLACEMENT, ETC).