57
APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)
LEGEND
SCREEN NAME POINT NAME
PASSWORD
LEVEL
EDITABLE RANGE DEFAULT NOTES
Configuration
Unit
Configuration
Fan Mode
Admin Password
level access only
X
Auto/Continuous/
Always On
Continuous
Auto= Intermittant operation during both
occupied and unoccupied periods/
Continuous = Intermittant during unoccupied
periods and continuous during occupied
periods/Always on = fan operates
continuously during both occupied and
unoccupied periods
Fan On Delay X 0 - 30 sec 10 sec
Defines the delay time before the fan begins
to operate after heating or cooling is started
Fan Off Delay X 0 - 180 sec 45 sec
Defines the amount of time the fan will
continue to operate after heating or
cooling is stopped
Heating Enable X Disable/Enable Enable
Provides capability to manually
disable heating operation
Cooling Enable X Disable/Enable Enable
Provides capability to manually
disable cooling operation
Minimum SAT in
Cooling
X40 - 60 F50 F
Defines the minimum acceptable operating
temperature for the Supply Air
Maximum SAT in
Heating
X 80 - 140 F 110 F
Defines the maximum acceptable operating
temperature for the Supply Air
Damper Ventilation
Position
X 0 - 100% 100%
Normally set to 100% if 2 position damper
type or set to minimum ventilation position if
damper type = DCV
DCV Maximum Vent
Position
X 0 - 100% 100%
Usually set at 100% - Used to limit maximum
damper opening in DCV mode
Filter Alarm Timer X 0 - 9999 hrs 0 hrs Disables Filter Alarm if set to 0
Pushbutton Override X Disable/Enable Enable Enables Override Feature on Rnet sensor
SPT Sensor Set Point
Adjustment
X Disable/Enable Enable
Enables Set Point adjustment capability
on Rnet Sensor
Lockout Cooling if
OAT <
X -65 - 80 F -65 F
Cooling is locked out when OAT is less than
configured value and OAT is actively being
broadcast
Lockout Heating if
OAT >
X 35 - 150 F 150 F
Heating is locked out when OAT is greater
than configured value and OAT is actively
being broadcast
Power Fail Restart
Delay
X 0 - 600 sec 60 sec Delay before equipment starts
Occupancy Schedules X Disable/Enable Enable Enables unit occupied
Set Point Separation X 2 - 9 F 4 F
Used to enforce minimum
set point separation
Configuration
Service
Test
Test Mode
Admin Password
level access only
X Disable/Enable Disable
Used to enable test mode. Will automatically
reset to disable after 1 hour
Fan Test X Disable/Enable Disable
Used to test all fan speeds. Sequences fan
from low to high and operates each speed for
1 minute. Resets to disable on completion
Fan Speed
Off/Low Speed/Medium
Speed/High Speed/On
Displays current fan operation
Compressor Test X Disable/Enable Disable
Used to test compressor cooling and heating
operation. Sequences cooling stage 1, then
stage 2, then heating stage 2 and reduces
capacity to stage 1. Operates for 1 minute per
step. Resets to disable on completion.
Dehumidification Test X Disable/Enable Disable
Used to test dehumification mode -
Operates for 2 minutes. Resets to
disable on completion.
Testing Compressor
Inactive/Heating/Cooling/
Dehumidify/TimeGard
Wait
Displays compressor test mode
Aux Heating Test X Disable/Enable Disable
Used to test auxiliary heat.
Sequences fan on and enables
heating coil for 1 minute. Resets to
disable on completion
H
2
O Economizer Test X Disable/Enable Disable
Used to test entering/return air water loop
economizer coil operation. Sequences fan on
and opens economizer coil water valve for 1
minute. Resets to disable on completion
Preposition OA
Damper
X Disable/Enable Disable
Used to preposition OA damper
actuator to set proper preload
Open Vent
Damper 100%
X Disable/Enable Disable Used to test OA damper operation
SAT F Displays SAT
LCWT F
Displays Leaving Condenser
Water Temperature
BAS — Building Automation System
DCV — Demand Controlled Ventilation
IAQ — Indoor Air Quality
OAT — Outdoor Air Temperature
RH — Relative Humidity
SAT — Supply Air Temperature
SPT — Space Temperature
TPI — Third Party Integration