Carrier 50PG03-07 Air Conditioner User Manual


 
19
Table 3 -- Electrical Data -- Units With Optional Powered Convenience Outlet (cont)
UNIT
50PG
NOMINAL
POWER S UPPLY
Volts-Ph-Hz
VOL TAGE
RANGE
COMPRESSOR
OFM
FLA
POWER
EXHAUST
FLA
IFM
TYPE
IFM
FLA
ELECTRICHEAT POWER SUPPLY
DISCONNECT
SIZE
Min Max RLA LRA FLA
Nominal
kW*
MCA MOCP† FLA LRA
05
(cont)
460-3-60 414 506 7.1 46 0.5
Low 2. 1
13.7 15 14 55
5.8 5.0 13.7 15 14 55
8.7 7.5 16.3 20 15 55
11.5 10.0 19.8 20 18 55
17.3 15.0 27.0 30 25 55
23.1 20.0 34.3 35 32 55
High 2.6
14.2 15 14 64
5.8 5.0 14.2 15 14 64
8.7 7.5 16.9 20 16 64
11.5 10.0 20.4 25 19 64
17.3 15.0 27.6 30 25 64
23.1 20.0 34.9 35 32 64
0.6
Low 2. 1
14.3 15 14 56
5.8 5.0 14.3 15 14 56
8.7 7.5 17.0 20 16 56
11.5 10.0 20.5 25 19 56
17.3 15.0 27.8 30 26 56
23.1 20.0 35.0 40 32 56
High 2.6
14.8 15 15 65
5.8 5.0 14.8 15 15 65
8.7 7.5 17.6 20 16 65
11.5 10.0 21.1 25 19 65
17.3 15.0 28.4 30 26 65
23.1 20.0 35.6 40 33 65
575-3-60 518 633 5.1 34 0.5
Low 2. 1
10.7 15 11 42
9.2 10.0 16.3 20 15 42
13.9 15.0 22.1 25 20 42
18.5 20.0 27.9 30 26 42
High 2.0
10.6 15 11 48
9.2 10.0 16.1 20 15 48
13.9 15.0 22.0 25 20 48
18.5 20.0 27.8 30 26 48
1.4
Low 2. 1
12.1 15 12 44
9.2 10.0 18.0 20 17 44
13.9 15.0 23.9 25 22 44
18.5 20.0 29.6 30 27 44
High 2.0
12.0 15 12 50
9.2 10.0 17.9 20 16 50
13.9 15.0 23.8 25 22 50
18.5 20.0 29.5 30 27 50
06
208/230-1-60 187 253 26.9 145 1.5
Low 4. 9
44.8/ 44.8 50/ 50 44/44 165/165
17.3/ 20.0 3.8/ 5.0 44.8/ 44.8 50/ 50 44/44 165/165
26.0/ 30.0 5.6/ 7.5 44.8/ 49.6 50/ 50 44/46 165/165
34.7/ 40.0 7.5/10.0 55.5/ 62.1 60/ 70 51/57 165/165
52.0/ 60.0 11.3/15.0 77. 1/ 87.1 80/ 90 71/80 165/165
69.3/ 80.0 15.0/20.0 98. 8/112.1 100/125 91/103 165/165
86.7/100.0 18.8/25.0 120.5/137.1 125/150 111/126 165/165
High 7.0
46.9/ 46.9 50/ 50 46/ 46 190/190
17.3/ 20.0 3.8/ 5.0 46.9/ 46.9 50/ 50 46/ 46 190/190
26.0/ 30.0 5.6/ 7.5 47.3/ 52.3 50/ 60 46/ 48 190/190
34.7/ 40.0 7.5/10.0 58.1/ 64.8 60/ 70 53/ 60 190/190
52.0/ 60.0 11.3/15.0 79. 8/ 89.8 80/ 90 73/ 83 190/190
69.3/ 80.0 15.0/20.0 101.4/114.8 110/125 93/106 190/190
86.7/100.0 18.8/25.0 123.1/139.8 125/150 113/129 190/190
1.4
Low 4. 9
46.2/ 46.2 50/ 50 45/ 45 167/167
17.3/ 20.0 3.8/ 5.0 46.2/ 46.2 50/ 50 45/ 45 167/167
26.0/ 30.0 5.6/ 7.5 46.4/ 51.4 50/ 60 45/ 47 167/167
34.7/ 40.0 7.5/10.0 57.3/ 63.9 60/ 70 53/ 59 167/167
52.0/ 60.0 11.3/15.0 78. 9/ 88.9 80/ 90 73/ 82 167/167
69.3/ 80.0 15.0/20.0 100.5/113.9 110/125 92/105 167/167
86.7/100.0 18.8/25.0 122.3/138.9 125/150 112/128 167/167
High 7.0
48.3/ 48.3 50/ 50 48/ 48 192/192
17.3/ 20.0 3.8/ 5.0 48.3/ 48.3 50/ 50 48/ 48 192/192
26.0/ 30.0 5.6/ 7.5 49.0/ 54.0 50/ 60 48/ 50 192/192
34.7/ 40.0 7.5/10.0 59.9/ 66.5 60/ 70 55/ 61 192/192
52.0/ 60.0 11.3/15.0 81. 5/ 91.5 90/100 75/ 84 192/192
69.3/ 80.0 15.0/20.0 103.1/116.5 110/125 95/107 192/192
86.7/100.0 18.8/25.0 124.9/141.5 125/150 115/130 192/192
LEGEND
FLA --- Full Load Amps
HACR --- Heating, Air Conditioningand Refrigeration
IFM --- Indoor(Evaporator) FanMotor
LRA --- Locked Rotor Amps
MCA --- MinimumCircuitAmps
MOCP --- Maximum Overcurrent Protection
NEC --- National Electrical Code
OFM --- Outdoor (Condenser)FanMotor
RLA --- RatedLoadAmps
*Heatercapacity (kW)is basedon heatervoltage of208v, 240v, 480v, or600v. Ifpower
distribution voltage to unitvariesfromrated heatervoltage,heaterkW will vary accord-
ingly.
{ Fuse or HACR circuit breaker .
NOTES:
1. In c ompliance withNECrequirementsfor multimotorandcombinationloadequipment(refer
toNECArticles430and440),theovercurrentprotectivedevicefortheunitshallbefuse or
HACRbreaker. Canadianunitsmaybefuse or circuitbreaker.
2. Unbalanced3-Phase Supply Voltage
Neveroperate amotorwhereaphaseimbalance insupply v oltageisgreaterthan 2%.Use
thefollowing formulatodetermine the percentageof voltageimbalance.
%VoltageImbalance =100x
maxvoltagedeviatio nfromaveragevoltage
average v oltage
Example: Supply voltage is 230---3---60
AB=224v
BC=231v
AC=226v
Average Voltage=
224+231+226
3
681
3
=
227
=
Determinemaximumdeviation from average voltage.
(AB)227–224 =3v
(BC) 231–227=4v
(AC)227–226 =1v
Maximumdeviationis4v.
Determinepercentof voltage imbalance.
%VoltageImbalance = 100x
4
227
=1.76%
Thisamountof phase imbalance issatisfactory asitisbelow themaximum allowable2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utilitycompany immediately.
50PG03--07