Carrier 50PG03-07 Air Conditioner User Manual


 
14
Table 2 -- Electrical Data -- Units Without Optional Convenience Outlet (cont)
UNIT
50PG
NOMINAL
POWER SUPPLY
Volts-Ph-Hz
VOLTAGE
RANGE
COMPRESSOR
OFM
FLA
POWER
EXHAUST
FLA
IFM
TYPE
IFM
FLA
ELECTRIC HEAT POWER SUPPLY
DISCONNECT
SIZE
Min Max RLA LRA FLA
Nominal
kW*
MCA MOCP† FLA LRA
05
(cont)
460-3-60 414 506 7.1 46 0.5
Low 2. 1
11.5 15 11 53
5.8 5.0 11.5 15 11 53
8.7 7.5 13.5 15 12 53
11.5 10.0 17.0 20 16 53
17.3 15.0 24.3 25 22 53
23.1 20.0 31.5 35 29 53
High 2.6
12.0 15 12 62
5.8 5.0 12.0 15 12 62
8.7 7.5 14.1 15 13 62
11.5 10.0 17.6 20 16 62
17.3 15.0 24.9 25 23 62
23.1 20.0 32.1 35 30 62
0.6
Low 2. 1
12.1 15 12 54
5.8 5.0 12.1 15 12 54
8.7 7.5 14.3 15 13 54
11.5 10.0 17.8 20 16 54
17.3 15.0 25.0 30 23 54
23.1 20.0 32.3 35 30 54
High 2.6
12.6 15 12 63
5.8 5.0 12.6 15 12 63
8.7 7.5 14.9 15 14 63
11.5 10.0 18.4 20 17 63
17.3 15.0 25.6 30 24 63
23.1 20.0 32.9 35 30 63
575-3-60 518 633 5.1 34 0.5
Low 2. 1
9.0 15 9 40
9.2 10.0 14.1 15 13 40
13.9 15.0 20.0 25 18 40
18.5 20.0 25.8 30 24 40
High 2.0
8.9 15 9 46
9.2 10.0 14.0 15 13 46
13.9 15.0 19.9 20 18 46
18.5 20.0 25.6 30 24 46
1.4
Low 2. 1
10.4 15 10 42
9.2 10.0 15.9 20 15 42
13.9 15.0 21.8 25 20 42
18.5 20.0 27.5 30 25 42
High 2.0
10.3 15 10 48
9.2 10.0 15.8 20 14 48
13.9 15.0 21.6 25 20 48
18.5 20.0 27.4 30 25 48
06
208/230-1-60 187 253 26.9 145 1.5
Low 4. 9
40.0/ 40.0 45/ 45 38/38 160/160
17.3/ 20.0 3.8/ 5.0 40.0/ 40.0 45/ 45 38/38 160/160
26.0/ 30.0 5.6/ 7.5 40.0/ 43.6 45/ 45 38/40 160/160
34.7/ 40.0 7.5/10.0 49.5/ 56.1 50/ 60 46/52 160/160
52.0/ 60.0 11.3/15.0 71. 1/ 81.1 80/ 90 65/75 160/160
69.3/ 80.0 15.0/20.0 92. 8/106.1 100/110 85/98 160/160
86.7/100.0 18.8/25.0 114.5/131.1 125/150 105/121 160/160
High 7.0
42.1/ 42.1 45/ 45 41/41 185/185
17.3/ 20.0 3.8/ 5.0 42.1/ 42.1 45/ 45 41/41 185/185
26.0/ 30.0 5.6/ 7.5 42.1/ 46.3 45/ 50 41/43 185/185
34.7/ 40.0 7.5/10.0 52.1/ 58.8 60/ 60 48/54 185/185
52.0/ 60.0 11.3/15.0 73. 8/ 83.8 80/ 90 68/77 185/185
69.3/ 80.0 15.0/20.0 95. 4/108.8 100/110 88/100 185/185
86.7/100.0 18.8/25.0 117.1/133.8 125/150 108/123 185/185
1.4
Low 4. 9
41.4/ 41.4 45/ 45 40/40 162/162
17.3/ 20.0 3.8/ 5.0 41.4/ 41.4 45/ 45 40/40 162/162
26.0/ 30.0 5.6/ 7.5 41.4/ 45.4 45/ 50 40/42 162/162
34.7/ 40.0 7.5/10.0 51.3/ 57.9 60/ 60 47/53 162/162
52.0/ 60.0 11.3/15.0 72. 9/ 82.9 80/ 90 67/76 162/162
69.3/ 80.0 15.0/20.0 94. 5/107.9 100/110 87/99 162/162
86.7/100.0 18.8/25.0 116.3/132.9 125/150 107/122 162/162
High 7.0
43.5/ 43.5 50/ 50 42/42 187/187
17.3/ 20.0 3.8/ 5.0 43.5/ 43.5 50/ 50 42/42 187/187
26.0/ 30.0 5.6/ 7.5 43.5/ 48.0 50/ 50 42/44 187/187
34.7/ 40.0 7.5/10.0 53.9/ 60.5 60/ 70 50/56 187/187
52.0/ 60.0 11.3/15.0 75. 5/ 85.5 80/ 90 69/79 187/187
69.3/ 80.0 15.0/20.0 97. 1/110.5 100/125 89/102 187/187
86.7/100.0 18.8/25.0 118.9/135.5 125/150 109/125 187/187
LEGEND
FLA --- Full Load Amps
HACR --- Heating, Air Conditioningand Refrigeration
IFM --- Indoor(Evaporator) FanMotor
LRA --- Locked Rotor Amps
MCA --- MinimumCircuitAmps
MOCP --- Maximum Overcurrent Protection
NEC --- National Electrical Code
OFM --- Outdoor (Condenser)FanMotor
RLA --- RatedLoadAmps
*Heatercapacity (kW)is basedon heatervoltage of208v, 240v, 480v, or600v. Ifpower
distribution voltage to unitvariesfromrated heatervoltage,heaterkW will vary accord-
ingly.
{ Fuse or HACR circuit breaker .
NOTES:
1. In c ompliance withNECrequirementsfor multimotorandcombinationloadequipment(refer
toNECArticles430and440),theovercurrentprotectivedevicefortheunitshallbefuse or
HACRbreaker. Canadianunitsmaybefuse or circuitbreaker.
2. Unbalanced3-Phase Supply Voltage
Neveroperate amotorwhereaphaseimbalance insupply v oltageisgreaterthan 2%.Use
thefollowing formulatodetermine the percentageof voltageimbalance.
%VoltageImbalance =100x
maxvoltagedeviatio nfromaveragevoltage
average v oltage
Example: Supply voltage is 230---3---60
AB=224v
BC=231v
AC=226v
Average Voltage=
224+231+226
3
681
3
=
227
=
Determinemaximumdeviation from average voltage.
(AB)227–224 =3v
(BC) 231–227=4v
(AC)227–226 =1v
Maximumdeviationis4v.
Determinepercentof voltage imbalance.
%VoltageImbalance = 100x
4
227
=1.76%
Thisamountof phase imbalance issatisfactory asitisbelow themaximum allowable2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utilitycompany immediately.
50PG03--07