Carrier 50HG014-028 Air Conditioner User Manual


 
20
Set heat anticipator settings as shown in Table 3.
Table 3 Heat Anticipator Settings
Settings may be changed slightly to provide a greater degree
of comfort for a particular installation.
Step 8 Install Outdoor Air Hood
Perform the
following procedure to install the outdoor-air hood:
1. Remove blank panel from return end of unit (hood sec-
tion). Save the screws. See Fig. 15 for shipping location
of components.
2. Hood sides are fastened to sides of outdoor air opening.
Remove the hood sides and save the screws (3 each side).
3. Remove the bracket holding the bottom half of the hood
in the shipping position. Remove the hood bottom half
and filters (or manual dampers on units so equipped)
from outdoor section.
NOTE: On units without economizers, the components
are attached to the unit basepan. To access the compo-
nents, remove the panel below the outdoor air intake
section.
4. Remove inner filter track from shipping position in out-
door section. Position inner filter track so the track is fac-
ing outward from the unit. Install the filter track with
4 screws provided.
5. Apply seal strip (provided) to back flange of both hood
sides where hood side connects to the unit back panel.
See Fig. 16.
6. Apply seal strip (provided) to top flange of both hood
sides where hood sides connect to the hood top panels.
See Fig. 16.
7. Install hood sides to the back panels using the screws from
Step 2. The sloped flanges point outward. The drip edges
of the side panels should face outward as well. The filter
guides should face inward to hold the filters in place. See
Fig. 16.
8. Apply seal strip along the entire length of the bottom
flange of the hood top. See Fig. 16.
9. Install the bottom part of the hood top using 4 screws pro-
vided. See Fig. 16.
10. Remove the packaging from filters (3) and install into the
filter tracks. Slide the filters to the sides then place the last
filter into the center of the filter track.
NOTE: For units with manual dampers, replace the end filters
with the manual dampers. Install the filter in the center
between the manual dampers.
11. Install the filter retainer track along the bottom edge of the
outdoor air hood using 4 screws provided. See Fig. 16.
12. Install top section of the outdoor air hood using 9 screws
provided. See Fig. 16. See Fig. 17 for a picture of the
assembled outdoor air hood.
NOTE: For filter removal, remove the four screws holding the
filter retainer. The filters can then be removed, cleaned, or
replaced. Install the filters by reversing the procedure.
MANUAL DAMPER ASSEMBLY For units equipped
with manual dampers, the assembly process is similar to the out-
door air hood for units with economizers. There are two slide
dampers shipped with the unit to allow for manual setting of the
outside air volume. When assembling the hood, place one of the
manual slide dampers in each of the end positions and the re-
maining filter in the center position. The manual dampers can
then be moved to the appropriate position and then locked into
place using the screws mounted in the adjustment slots. See
Fig. 18.
UNIT SIZE
50HG
ELECTRIC
HEAT(kW)
STAGE 1
(W1) ON
STAGES 1AND 2
(W1 and W2) ON
Voltage Voltage
208/240 480 600 208/240 480 600
014
15 0.2 0.2 0.2 0.2 0.2 0.2
25 0.2 0.2 0.2 0.4 0.4 0.4
50 0.4 0.2 0.2 0.8 0.4 0.4
016-028
25 0.2 0.2 0.2 0.4 0.4 0.4
50 0.4 0.2 0.2 0.8 0.4 0.4
75 0.4 0.2 0.2 0.8 0.4 0.4
TB4
REMOVABLE JUMPER
1
2
3
45
6
7
8
THERMOSTATASSEMBLY
RH
RC
Y1 Y2
W1 W2 G C
L
X
R
Y1 Y2
W1 W2 G C X
COM
T1
T2
TH
SN
7
8
9
T-55 SPT
T-56 SPT
TB3
LEGEND
NOTE: The maximum wire size for TB1 is 2/0.
Fig. 12 Field Power Wiring Connections
EQUIP
Equipment
GND
Ground
NEC
National Electrical Code
TB
Terminal Board
Fig. 13 Field Control Thermostat Wiring
SPT
Space Temperature Sensor
Fig. 14 Field Control Space
Temperature Sensor Wiring
HOOD TOP
(BOTTOM HALF)
HOOD TOP
(TOPHALF)
HOOD
SIDE
HOOD
SIDE
RETURNAIR
SECTION
Fig. 15 Outdoor-Air Hood Compartment
Shipping Location