Table 2B Electrical Data (Units With Optional Convenience Outlet) (cont)
ELECTRIC HEAT BRANCH CIRCUIT FOR 208/240-V 75-kW ELECTRIC HEAT
FEEDER CIRCUIT FOR 208/230-V UNIT WITH 75-kW ELECTRIC HEAT
See Legend and Notes onpage10.
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM
ELECTRIC
HEAT
IFM
POWER
EXHAUST
POWER
SUPPLY
DISCONNECT
SIZE
No.1 No.2 No.3
Min Max RLA LRA RLA LRA RLA LRA Qty Hp
FLA
(ea)
kW FLA Hp FLA Qty Hp
FLA
(ea)
MCA MOCP* FLA
016
208/230 187 253 16.7 130.0 16.7 130.0 16.7 130.0 4.0
1
/
4
1.5
——
3.7 10.6/ 9.6
—— — 76/ 75 90/ 90 80/ 80
2 1.0 5.9 88/ 87 100/100 100/ 90
5.0 16.7/15.2
—— — 82/ 80 90/ 90 90/ 90
2 1.0 5.9 94/ 92 110/100 100/100
19/25 52/ 60
3.7 10.6/ 9.6
—— — 85/ 93 90/100 80/ 90
2 1.0 5.9 99/108 100/110 100/100
5.0 16.7/15.2
—— — 92/100 100/110 90/ 90
2 1.0 5.9 107/115 110/125 100/110
38/50 104/120
3.7 10.6/ 9.6
—— — 150/138 150/150 150/150
2 1.0 5.9 164/153 175/175 150/175
5.0 16.7/15.2
—— — 157/145 175/150 150/175
2 1.0 5.9 172/160 175/175 175/175
56/75 156/180
3.7 10.6/ 9.6
—— — 76/ 75 90/ 90 80/ 80
2 1.0 5.9 88/ 87 100/100 100/ 90
5.0 16.7/15.2
—— — 82/ 80 90/ 90 90/ 90
2 1.0 5.9 94/ 92 110/100 100/100
460 414 506 9.0 70.0 9.0 70.0 9.0 70.0 4.0
1
/
4
0.7
——
3.7 4.8
—— — 40 45 40
21.03.1 46 50 50
5.0 7.6
—— — 43 50 45
21.03.1 49 50 60
25 30
3.7 4.8
—— — 47 50 45
21.03.1 55 60 50
5.0 7.6
—— — 51 60 45
21.03.1 59 60 60
50 60
3.7 4.8
—— — 70 80 80
21.03.1 78 80 90
5.0 7.6
—— — 73 80 80
21.03.1 81 90 90
75 90
3.7 4.8
—— — 100 110 110
2 1.0 3.1 108 125 125
5.0 7.6
—— — 103 125 125
2 1.0 3.1 111 125 125
575 518 633 7.0 55.0 7.0 55.0 7.0 55.0 4.0
1
/
4
0.7
——
3.0 3.9
—— — 32 35 35
21.03.1 39 45 40
5.0 6.1
—— — 35 40 35
21.03.1 41 50 45
25 24
3.0 3.9
—— — 39 40 35
21.03.1 46 50 40
5.0 6.1
—— — 41 45 35
21.03.1 49 50 45
48 46
3.0 3.9
—— — 66 70 60
21.03.1 74 80 70
5.0 6.1
—— — 69 70 60
21.03.1 77 80 70
78 75
3.0 3.9
—— — 84 90 100
2 1.0 3.1 91 100 100
5.0 6.1
—— — 86 100 100
2 1.0 3.1 94 100 110
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3Ph, 60Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM
ELECTRIC
HEAT
IFM
POWER
EXHAUST
POWER
SUPPLY
DISCONNECT
SIZE
No.1 No.2 No.3
Min Max RLA LRA RLA LRA RLA LRA Qty Hp
FLA
(ea)
kW FLA Hp FLA Qty Hp
FLA
(ea)
MCA MOCP* FLA
016 208/240 187 253 NA NA NA NA NA NA NA NA NA 56/75 156/180 NA NA NA NA NA 156/180 175/200 200/225
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM
ELECTRIC
HEAT
IFM
POWER
EXHAUST
POWER
SUPPLY
DISCONNECT
SIZE
No. 1 No. 2 No. 3
Min Max RLA LRA RLA LRA RLA LRA Qty Hp
FLA
(ea)
kW FLA Hp FLA Qty Hp
FLA
(ea)
MCA MOCP* FLA
016 208/230 187 253 16.7 130.0 16.7 130.0 16.7 130.0 4.0 1/4 1.5 56/75 156/180
3.7 10.6/ 9.6
—— —176/198 200/225 200/225
2 1.0 5.9 190/213 200/225 225/250
5.0 16.7/15.2
—— —183/205 200/225 200/225
2 1.0 5.9 198/220 200/225 225/250